Manual of SR288 intelligent controller
43
continuously exceeded the disinfection temperature TDIS for the entire disinfection period
DDIS. Thermal disinfection can only be completed when the disinfection temperature is
exceeded for the duration of the disinfection period without any interruption.
The monitoring period PDIS starts as soon as the temperature at the allocated sensor falls
below the disinfection temperature TDIS, once the monitoring period PDIS ends, disinfection
period SDIS starts, and the allocated reference relay activates the after-heating, when tank
temperature exceeds the disinfection temperature, disinfection phase DDIS starts and
disinfection heating time countdowns, countdown finishes, disinfection heating finishes.
Menu structure
Menu
Submenu Factory
set
Adjustable
range
Step
per
adjust
Description
OTDI
OFF
ON/OFF
Disinfection function
PDIS
7d
0-30d
1d
Time
section
of
disinfection
monitoring
DDIS
10min
1-180
1min
Heating time of disinfection
TDIS
70
o
C
0-90
o
C
1
o
C
Temperature of disinfection
SDIS
18:00
00:00-21:00 1:00
Start time of disinfection
Function setting
►Press “▲”, “OTDI” displays on the screen
►Press “SET”, “OTDI OFF” display
►Press “SET”, “OFF” blinks
►Press “▲/▼”, to activate this function, “OTDI ON” displays
►Press “SET” or “ESC” to save the setting
►Press “▲”, “PDIS 7” displays
►Press “SET”, “7” blinks
►Press “▲/▼”, to adjust the days for disinfection monitoring,