Manual of SR288 intelligent controller
45
►Press “▲/▼” to activate this function, “INVE ON” displays
►Press “SET” or “ESC” to save the setting
7.11 OHQM Thermal quantity measurement
The thermal quantity measurement can be carried out in 3 different ways:
Fixed flow rate ( use flow meter with glass window)
With Granados flow rotor VFS
With rotary vane flow mater FRT
Thermal quantity measurement with fixed flow rate value
The thermal quantity measurement calculation (estimation) uses the temperature difference
between the flow sensor T6 and return sensorT5 and the entered flow rate (at 100 % pump
speed).
Note:
sensor of flow and return pipe for thermal quantity measurement is default set
in solar system, it can not be reset.
Under menu FTYP to set the flow rate type to 1
Read the flow rate (l/min) and enter it in the
FMAX menu
Under menu
MEDT
and
MED%
to set the antifreeze medium type and concentration of the
heat transfer fluid
Antifreeze type:
0: Water
1: Propylene glycol
2: Ethylene glycol
3: Tyfocol LS / G-LS
Thermal quantity measurement with Grundfos Direct Sensor VFS
The thermal quantity measurement uses the temperature difference between flow sensor T6
and return sensor TVFS and the flow rate transmitted by the VFS sensor.
TVFS: Temperature of Grundfos Direct sensor VFS
Note:
1.
Sensor of flow and return pipe for thermal quantity
measurement is default set in the solar system, it can
not be reset.
2.
Flow checking function is only available when a VFS
type Grundfos Direct Sensor is connected to the