35
Character
Name, Function, Setting Range
Default Value
Remote/Local
Local
• SV can be set with either the Remote or Local method.
• Available when the External setting input is selected from the Block function (Console software).
•
: Local (The SV can be set by the front keypad as usual.)
: Remote (The SV can be set in analog by external remote operation.)
External setting scaling high limit
1370
• Sets the high limit value when External setting input is selected from the Block function
(Console software). (e.g. For 4 to 20 mA DC, the value corresponds to 20 mA input.)
When the Cascade control spec is selected, this sets the high limit value corresponding to
the master (CH2) MV 100 %.
For Potentiometer input spec, this sets the Potentiometer scaling high limit value.
Available for Potentiometer input spec or when External setting input or Cascade control
spec is selected from the Block function (Console software).
• Setting range: External setting scaling low limit to Input range high limit
External setting scaling low limit
-200
• Sets the low limit value when External setting input is selected from the Block function
(Console software). (e.g. For 4 to 20 mA DC, the value corresponds to 4 mA input.)
When the Cascade control spec is selected, this sets the low limit value corresponding to
the master (CH2) MV 0 %.
For Potentiometer input spec, this sets the Potentiometer scaling low limit value.
Available for Potentiometer input spec or when External setting input or Cascade control
spec is selected from the Block function (Console software).
• Setting range: Input range low limit to External setting scaling high limit
Remote bias
0
• Sets remote bias value.
During remote action, the control desired value adds SV to the remote bias value.
Available when External setting input is selected from the Block function (Console
software).
• Setting range: Converted value of
20 % of the input span
DC current, voltage input:
20 % of the scaling span (The placement of the decimal point
follows the selection.)
Transmission output
• Selects transmission output type.
Selection from the Block
function
Available only when Transmission output is selected from the Block function (Console software).
•
: PV transmission
: SV transmission
: MV transmission
Transmission output high limit
• Sets the Transmission output high limit value.
PV, SV transmission: 1370
MV transmission: 100.0 %
(For 4 to 20 mA DC, the value correponds to 20 mA output.)
Available when Transmission output is selected from the Block function (Console software).
• Setting range:
PV, SV transmission : Transmission output low limit to Input range high limit
MV transmission
: Transmission output low limit to 105.0 (%)
Transmission output low limit
• Sets the Transmission output low limit value.
PV, SV transmission: -200
MV transmission: 0.0 %
(For 4 to 20 mA DC, the value correponds to 4 mA output.)
Available when Transmission output is selected from the Block function (Console software).
• Setting range:
PV, SV transmission : Input range low limit to Transmission output high limit
MV transmission
: -5.0 % to Transmission output high limit