26
SV
OUT2 proportional band
Air cooling
Oil cooling
Water cooling
Character
Name, Function, Setting Range
Default Value
Emissivity
0.900 times
• Sets infrared emissivity.
Setting characters and PV are alternately indicated on the CH1 PV/SV display.
Available only for Infrared thermocouple input.
• Setting range: 0.100 to 1.000 times
Output high limit
100 %
• Sets the output high limit value.
Not available if output is in ON/OFF control.
If Heating/Cooling control output is selected from the Block function (Console software),
CH1 output will be OUT1, and CH2 output will be OUT2.
• Setting range: Output low limit to 100 %
(DC current output: Output low limit to 105 %)
Output low limit
0 %
• Sets the output low limit value.
Not available if output is in ON/OFF control.
If Heating/Cooling control output is selected from the Block function (Console software),
CH1 output will be OUT1, and CH2 output will be OUT2.
• Setting range: 0 % to Output high limit
(DC current output: -5 % to Output high limit)
Output ON/OFF hysteresis
1.0
• Sets the output ON/OFF hysteresis.
Available only when output is in ON/OFF control
If Heating/Cooling control output is selected from the Block function (Console software),
CH1 output will be OUT1, and CH2 output will be OUT2.
• Setting range: 0.1 to 100.0
( ),
DC current, voltage input: 1 to 1000 (The placement of the decimal point follows the
selection.)
OUT2 action mode
Air cooling
• Selects OUT2 action from air, oil and water cooling.
• Available when Heating/Cooling control output is
selected from the Block function (Console
software).
Not available if OUT2 is in ON/OFF control.
•
: Air cooling (linear characteristic)
: Oil cooling (1.5th power of the linear characteristic)
: Water cooling (2nd power of the linear characteristic)
(Fig.8.2-1)
OUT2 high limit
100 %
• Sets OUT2 high limit value.
• Available when Heating/Cooling control output is selected from the Block function
(Console software).
Not available if OUT2 is in ON/OFF control.
• Setting range: OUT2 low limit to 100 %
(DC current output: OUT2 low limit to 105 %)
OUT2 low limit
0 %
• Sets OUT2 low limit value.
• Available when Heating/Cooling control output is selected from the Block function
(Console software).
Not available if OUT2 is in ON/OFF control.
• Setting range: 0 % to OUT2 high limit
(DC current output: -5 % to OUT2 high limit)
OUT2 ON/OFF hysteresis
1.0
• Sets ON/OFF hysteresis for OUT2.
Available when Heating/Cooling control output is selected from the Block function
(Console software), and when OUT2 is in ON/OFF control.
• Setting range: 0.1 to 100.0
( ),
DC current, voltage input: 1 to 1000 (The placement
of the decimal point follows the selection.)