6
1.2 Rated scale
(Table 1.2-1)
Input type
Input range
Resolution
-200 to 1370
-320 to 2500
1 ( )
K
-199.9 to 400.0
-199.9 to 750.0
0.1 ( )
J
-200 to 1000
-320 to 1800
1 ( )
R
0 to 1760
0 to 3200
1 ( )
S
0 to 1760
0 to 3200
1 ( )
B
0 to 1820
0 to 3300
1 ( )
E
-200 to 800
-320 to 1500
1 ( )
T
-199.9 to 400.0
-199.9 to 750.0
0.1 ( )
N
-200 to 1300
-320 to 2300
1 ( )
PL-
0 to 1390
0 to 2500
1 ( )
Thermo-
couple
C (W/Re5-26) 0 to 2315
0 to 4200
1 ( )
-199.9 to 850.0
-199.9 to 999.9
0.1 ( )
Pt100
-200 to 850
-300 to 1500
1 ( )
-199.9 to 500.0
-199.9 to 900.0
0.1 ( )
RTD
JPt100
-200 to 500
-300 to 900
1 ( )
4 to 20mA DC -1999 to 9999 *1, *2
1
0 to 20mA DC -1999 to 9999 *1, *2
1
0 to 1V DC
-1999 to 9999 *1
1
0 to 10V DC
-1999 to 9999 *1
1
1 to 5V DC
-1999 to 9999 *1
1
DC
current
DC
voltage
0 to 5V DC
-1999 to 9999 *1
1
(*1) For DC current and voltage inputs, scaling and decimal point place change are
possible.
(*2) For DC current input, 50 shunt resistor (sold separately) must be installed.
1.3 How to read the model nameplate
Warning
Do not take the inner assembly out or touch the terminal with the power
supply on when confirming the model nameplate.
Touching the terminal with the power switched ON may result in severe
injury or death due to Electric Shock.
Model nameplates are attached to the case and the left side of the inner assembly.
[Example]
PCD–33A–R/M
C5
MULTI–RANGE
No. xxxxxx
(Fig. 1.3-1)
Model name: PCD-33A-R/M
Option: C5 (Serial communication)
Instrument number: Only indicated on the
inner assembly.
Содержание PCD-33A