Circuit isolation configuration
When the control output is non-contact voltage output type or DC current
output type, between A to B and A to C are not isolated.
Isolation resistance
10M or greater at 500V DC for other combinations except those mentioned above
Dielectric strength
Between input terminal and ground terminal, 1.5kV AC for 1 minute
Between input terminal and power terminal, 1.5kV AC for 1 minute
Between output terminal and ground terminal, 1.5kV AC for 1 minute
Between output terminal and power terminal, 1.5kV AC for 1 minute
Between power terminal and ground terminal, 1.5kV AC for 1 minute
Weight
: Approx. 370
g
External dimension
: 96 x 96 x 100mm (W x H x D)
Material
: Case, Flame resistant resin
Color
: Case, Light gray
Attached functions
: Setting value lock function, Sensor correction function,
Power failure countermeasure, Self-diagnosis,
Automatic cold junction temperature compensation,
Burnout function (overscale), Input burnout, Warm-up indication
Accessories
: Mounting bracket
1 set
Instruction manual
1 copy
Terminal cover
2 pieces (When the option TC is applied.)
10.2 Optional specifications
Serial communication (Option code: C5)
External operation function cannot be used if option [C5] is applied.
The following operations can be executed from the external computer.
(1) Reading and setting of Step SV, Step time, PID values and various setting values.
(2) Reading of the input value and the action status.
(3) Change of the functions.
Alarm 2 (A2) output or
Isolated power output (P24)
A
Power
supply
Control
output
(OUT)
Communication
Alarm 1 (A1)
output
Event output
Input
Isolated
External
operation
B
C
4
14
3
1
2
12
13
10
5
9
8
10
7
6
18
20
19
17
14
17
Содержание PCD-33A
Страница 1: ...INSTRUCTION MANUAL FOR PROGRAMMABLE CONTROLLER PCD 33A ...
Страница 62: ...62 5 7 6 8 9 ...