14
5. Setup
5.1 Setup
Before using this controller, it is necessary to set up the Sensor type, Program control
start form, Alarm action, Control action, etc. according to the users’ conditions.
If the users’ specification is the same as the default value of the PCD-33A, it is not
necessary to set up the controller. Proceed to Chapter “6. Operations” (p.21)
Set up the controller after connecting terminals 2 and 3 for the power supply to this
instrument, referring to “4. Wiring connection” (p.10).
Setup is conducted in Auxiliary function setup mode 2.
The setting item and default value in Auxiliary function setting mode 2 are shown below
(Table 5.1-1).
(Table 5.1-1)
PV display
Setting/Selection item
Default value
(1)
Input type selection
Selects a sensor type and unit
/
.
Thermocouple K
-200 to 1370
(2)
Scaling high limit setting
Sets the scaling high limit value.
9999
(3)
Scaling low limit setting
Sets the scaling low limit value.
-1999
(4)
Decimal point place selection
Selects a decimal point place.
No decimal
point
(5)
PV filter time constant setting
Sets the PV filter time constant.
0.0 seconds
(6)
Step time unit selection
Selects the step time unit.
Hour:Minute
(7)
Step SV setting when control starts
Sets step SV when program control starts.
0
(8)
Program control start form selection
Selects the program control start form.
PV start
(9)
Control output high limit setting
Sets control output high limit.
100%
(10)
Control output low limit setting
Sets control output low limit.
0%
(11)
Control output ON/OFF action Hysteresis setting
Sets control output ON/OFF action hysteresis.
1.0
(12)
Alarm 1 (A1) action selection
Selects Alarm 1 (A1) action type.
No alarm action
(13)
Alarm 2 (A2) action selection
Selects Alarm 2 (A2) action type.
No alarm action
(14)
Alarm 1 (A1) Energized/Deenergized selection
Selects Alarm 1 (A1) Energized/Deenergized.
Energized
(15)
Alarm 2 (A2) Energized/Deenergized selection
Selects Alarm 2 (A2) Energized/Deenergized.
Energized
(16)
Alarm 1 (A1) hysteresis setting
Sets Alarm 1 (A1) hysteresis.
1.0
(17)
Alarm 2 (A2) hysteresis setting
Sets Alarm 2 (A2) hysteresis.
1.0
(18)
Alarm 1 (A1) action delayed timer setting
Sets Alarm 1 (A1) action delayed timer.
0 seconds