56
8.2.1 SV, Event Group (for Fixed Value Control)
Sets SV and Event (EVT1, EVT4, EVT5) in this group.
If ‘Set value memory’ is selected in [Event input allocation], the setting items
in this group can be set for the selected memory numbers.
To enter the ‘SV, Event group’, follow the procedure below.
(1)
Press the
key in PV/SV Display Mode.
The unit proceeds to the ‘SV, Event group’.
(2)
Press the
key. The unit proceeds to ‘SV1’.
Character
Name, Function, Setting Range
Factory Default
SV1
0
• Sets SV1.
• Setting range: Scaling low limit to Scaling high limit
EVT1 alarm value
0
• Sets EVT1 alarm value.
Setting the value to 0 or 0.0 disables the function (except
Process high and low alarm)
.
Not available if No event is selected.
Available only when Alarm output is selected in [Event output EVT1
allocation].
• Setting range: Refer to (Table 8.1.2-1) on p.53.
EVT1 high limit alarm value
0
• Sets EVT1 high limit alarm value.
Setting the value to 0 or 0.0 disables the function (except
Process high and Process low alarm)
.
Not available if No event is selected.
Available only when Alarm output is selected in [Event output EVT1
allocation].
For the independent alarms such as High/Low limits independent
and High/Low limit range independent, the EVT alarm value matches
the low limit side, and EVT high limit alarm value matches the high
limit side.
• Setting range: Refer to (Table 8.1.2-1) on p.53.
EVT4 alarm value
0
• Sets EVT4 alarm value.
Setting the value to 0 or 0.0 disables the function (except
Process high and Process low alarm)
.
Not available if No event is selected.
Available only when Alarm output is selected in [Event output EVT4
allocation].
• Setting range: Refer to (Table 8.1.2-1) on p.53.