47
Character
Name, Function, Setting Range
Factory Default
Backlight time
0 minutes
• Sets time to backlight from no operation status until backlight is
switched off.
When set to 0, the backlight remains ON.
Backlight relights by pressing any key while backlight is OFF.
• Setting range: 0 to 99 minutes
Bar graph
MV indication
• Selects an indication item (MV, DV, degree of valve opening or no
indication) on the bar graph. (See p.50.)
•
: MV indication
: DV indication
: No indication
: Degree of valve opening is indicated.
Deviation unit
1
• Sets deviation unit of positive (or negative) side for one division
of the bar graph. (See p.50.)
• Setting range: 1 to Converted value of 20% of input span