7.3 Engineering Group
7.3.1 Input Group
To enter the Input group, follow the procedure below.
(1)
Press the
key 4 times in PV/SV Display Mode.
The unit will enter the Engineering group.
(2)
Press the
key. The unit will proceed to the Input group.
(3)
Press the
key.
The unit will proceed to the ‘Input type’.
Character
Name, Function, Setting Range
Factory Default
Input type
K (-200 to 1370 )
• The input type can be selected from thermocouple (10 types), RTD
(2 types), Direct current (2 types) and DC voltage (8 types), and the unit
/ can be selected as well.
• If the input type is changed, scaling high and low limit also change
to the high and low limit value of the altered input range.
•
When changing the input from DC voltage to other inputs, remove
the sensor connected to this controller first, then change the input.
(If the input is changed with the sensor connected, the input circuit
may break.)
•
With DC voltage input, the (+) side input terminal number differs
as follows.
(+) side input terminal number of 0 to 5 V DC, 1 to 5 V DC, 0-10 V DC: 16
(+) side input terminal number of 0 to 10 mV DC, -10 to 10 mV DC,
0 to 50 mV DC, 0 to 100 mV DC, 0 to 1 V DC: 18
•
Input types
K
-200 to
1370
K
-200.0 to
400.0
J
-200 to
1000
R
0 to
1760
S
0 to
1760
B
0 to
1820
E
-200 to
800
T
-200.0 to
400.0
N
-200 to
1300
PL-
0 to
1390
C(W/Re5-26)
0 to
2315
Pt100
-200.0 to
850.0
JPt100
-200.0 to
500.0
Pt100
-200 to
850
JPt100
-200 to
500
Pt100
-100.0 to
100.0
Pt100
-100.0 to
500.0