42
7.3.6 Communication Group
Available when C, C5 option is added.
To enter the Communication group, follow the procedure below.
(1)
Set the
key 4 times in PV/SV Display Mode.
The unit will enter the Engineering group.
(2)
Press the
key. The unit will proceed to the Input group.
(3)
Press the
key several times until Communication group characters
appear.
(4)
Press the
key.
The unit will proceed to ‘Communication protocol’.
Character
Name, Function, Setting Range
Factory Default
Communication protocol
Shinko protocol
• Selects communication protocol.
•
: Shinko protocol
: MODBUS ASCII mode
: MODBUS RTU mode
Instrument number
0
• Sets the instrument number.
The instrument numbers should be set one by one when multiple
instruments are connected in Serial communication, otherwise
communication is impossible.
• Setting range: 0 to 95
Communication speed
9600 bps
• Selects a communication speed equal to that of the host computer.
•
: 9600 bps
: 19200 bps
: 38400 bps
Data bit/Parity
7 bits/Even
• Selects data bit and parity.
•
: 8 bits/No parity
: 7 bits/No parity
: 8 bits/Even
: 7 bits/Even
: 8 bits/Odd
: 7 bits/Odd
Stop bit
1
• Selects the stop bit.
•
: 1
: 2
SVTC bias
0
• Control desired value (SV) adds SVTC bias value to the value
received by the SVTC command.
• Available only when Shinko protocol is selected in [Communication
protocol].
• Setting range: Converted value of 20% of input span
DC voltage, current inputs: 20% of scaling span (The placement of
the decimal point follows the selection.)