20(29)
F.11
Shutdown alarm for the times of material shortage
Set the number of times that no material falling into the
hopper. The times of material shortage that it should alarm.
1.ENT key on the panel can be cancelled.
2.Turn on/off the power again.
Corresponding action: A.04
3
[F.10]-99
F.12
The time waiting for motor stoppage (suitable for sal-430 /
460) .
After motor starts, it only takes next action after the time
countdown is finished.
20 secs.
0-99
secs.
F.13
Buzzer alarm type
0:
Lasting alarm
1: Slow and interrupted alarm
2:Fast and interrupted alarm
0
0-2
F.14
Motor delay stop time
After [F.01] suction time is ended, the delay time before
motor stop.
0 secs.
0~999
secs.
F.15
Motor working time
Check motor working time and clear the time.
The method to clear the motor working time: Set the setting
value as 0, and press ENT key to cancel.
0
(unit:
10 hrs.)
0-999
Only 0
means
clearing
the time.
4.3 Alarm Program
Description of blender controller, alarm status and solution method
Panel
Code
Alarm Causes
Solution Method
Shortage alarm [F.10]
1. The set suction time is too short.
2. The materials can
’
t be absorbed.
3. Suction pipeline is blocked.
4. Pipeline suction is too small.
1) Add materials
2) Increase suction time
3) Shut down and check the pipe line.
When it sucks the materials again, the alarm will
dismiss or the ENT key on the panel can also be
cancelled or turn on the power again.
Filter warning
Filter screen blocking
1) Shut down and clean the filter screen
or replace filter screen.
The alarm will dismiss when it turns on/off the
power again or it can be cancelled by clicking the
ENT key on the panel.