14
6. Service Data
ELECTRIC SHOCK
WARNING
Never touch the output terminal during operation to avoid electric
shock. Always stop the engine and remove the starter key during a
service maintenance.
Stop the engine before you will start any maintenance!
6-1 Technical Specification
Items
Reference Value
Note
Insulation
Armature
winding
3MΩ or more
DC500V
Megger Tester
Exciter field
Preheat time
Approx. 1 sec. with coolant temperature
30
℃
(86
°
F) and a
pprox. 10 sec. with
coolant temperature -15
℃
(5
°
F)
Automatic
preheating system
Min. rpm at no load
1200min
-1
Max. rpm at no load
60Hz: 1800min
-1
Lubricant oil pressure
0.24~0.44MPa{2.5~4.5kgf/cm²}
Coolant temperature
70~95
℃
(158~203
°
F)
Frame temperature limit
within 80
℃
(176
°
F)
Sealed bearing temperature limit
within 80
℃
(176
°
F)
Speed regulation
Momentary
within 10%
Steady-state
deviation
within 5%
Voltage regulation
Momentary
within 20%
Steady-state
deviation
within 1.0%
Frequency
Idle: 40 Hz, Rated: 60 Hz
Variable voltage (60Hz)
197~255V
60
±
0.1Hz
Protective device
1
Low oil pressure
Working Pressure
0.0481MPa{0.5kgf/cm²}
Engine Stop
2
High water temp.
Working Temperature
115
℃
(239
°
F)
Engine Stop
3
Diagnosis
Engine Malfunction
-
-
4
Insufficient Battery
Charge
-
Battery voltage: below 8V
-
5
Over Speed
-
above 2070 min
-1
Engine Stop
6
Boost
Intake Temperature
85
℃
(185
°
F)
-
Содержание DGK11F
Страница 8: ...5 4 General 4 1 Appearance 4 2 Dimension Unit in the drawings below is shows by mm...
Страница 9: ...6 EXHAUST GAS OUTLET WATER OUTLET...
Страница 10: ...7 5 General Parts Description 5 1 Equipment...
Страница 11: ...8...
Страница 12: ...9...
Страница 16: ...13 Left Side Door Standard Accessory Owners Manual 1 copy Engine Warranty Manual 1 copy Starter Key 1 set 2 pcs...
Страница 30: ...10 Wiring Diagram 27...
Страница 31: ...28...