Parameter Description
Parameters
89
P.0~P.11.Starting address is H0000.
Mode
Starting
Address
Function
Starting address
Number of registers
Check
Stop
ASCII
H3A
H30 H31 H30 H33 H30H30 H30 H30 H30 H30 H30 H43 H46 H30
0D 0A
RTU
>=10ms
01
03
00
00
00
0C
45 CF
>=10ms
Step 2. After receiving and processing the data without error, the inverter will send a reply to
the position machine:
Mode
Starting
Address
Function
Number of data read
Read-out data
Check
Stop
ASCII
H3A
H30 H31
H30 H33
H31 H38
…12×4 char
4char
0D 0A
RTU
>=10ms
01
03
18
…12×2 byte
2byte
>=10ms
Example 5.
Rewrite the values of parameters P.0~P.11 by the inverter
Step 1. The position machine sends message to the inverter for writing the value of
P.0~P.11.
Mode
Starting
Addr
ess
Func
tion
Starting
address
Number of
registers
Data
volume
Write-in data
Check
Stop
ASCII
H3A
H30
H31
H31
H30
H30
H30
H30
H30
H30
H30
H30
H43
H31
H38
…N×4 char
4char
0D 0A
RTU
>=10ms
01
10
00
00
00
0C
18
…N×2 byte
2byte
>=10ms
Step 2. After receiving and processing the data without error, the inverter will send a reply to
the position machine:
Mode
Starting
Address
Function
Starting address
Number of registers
Check
Stop
ASCII
H3A
H30 H31
H31
H30
H30H30
H30
H30
H30
H30
H30
H43
H45 H33
0D 0A
RTU
>=10ms
01
10
00
00
00
0C
00 18
>=10ms