Parameter Description
Parameters
90
4. The list of communication references
●
The following references and data are set for carrying out assorted operation control and
monitoring.
Item
Shihlin
protocol
Reference
code
Modbus
Reference
code
Modbus
address
Data content and function description
Operation mode
read-out
H7B
H03
H1000
H0000: Communication mode
;
H0001: External mode
;
H0002: JOG Mode
;
H0003: Combination 1, combination 3 and
combination 5 modes
;
H0004: Combination 2 and combination 4
modes
Operation mode
write-in
HFB
H06/H10
Inverter status
monitoring
H7A
H03
H1001
H0000~H00FF
b8~b15
:
Preservation
b7
:
Abnormality occurred
b6
:
Frequency test
b5: Ended by restoring the default value of
the parameter
b4
:
Overloaded
b3
:
Reached the frequency
b2
:
During reverse rotation
b1
:
During forward rotation
b0
:
During rotation
Target
frequency
write-in
EEPROM
HEE
H06/H10
H1009
H0000~ HFDE8
:
0~650Hz
RAM
HED
H1002
Special monitor
select codes read out
H7D
H03
H1013
H0000~H0010
:
Monitor selected information
Special monitor select read out codes as
described in the special monitoring code table
(H0009 is reserved)
Special monitor
select codes write in
HF3
H06/H10
Monitor the external
operation condition
H7C
H03
H1012
H0000~H000F
:
b0
b3
b2
b1
b15~b4
RES
STF
STR
MRS
0000 0000 0000