background image

1

PAC

SJ95MA

E

BH79N063H03

INSTALLATION MANUAL FOR A-M CONVERTER

SAFETY PRECAUTIONS

After installation, make test operation and confirm that it works properly, and explain the safety precautions, operation method, and 

  maintenance to your customers. 
  Tell your customers to keep this installation manual together with operation manual with them, and when they give or sell this machine 
  to other person put this installation manual and operation manual with it.

Before starting installation, read the "Safety Precautions" described below.

The following precautions must be observed as it describes the serious matters for safety.

The safety precautions are described with the degree of danger.

WARNING

WARNING

CAUTION

When you handle wrong, it can lead to death or serious injury.

When you handle wrong, it can lead to injury or damage to building and furniture.

The installation must be done by dealer or qualified person.

If the customers do the installation by themselves and it is not perfectly 

  installed it can cause water leak, electric shock, or fire.

 

If the installation is not perfectly done, it can cause water leak, electric 

  shock, or fire.

The installation must be done in accordance with this manual.

Never try any modification.

For repair, ask your dealer.  

  If the machine is not modified or repaired completely, it can cause water 
  leak, electric shock, or fire.

Never move or reinstall the machine by the customers.

If the installation is not perfectly done, it can cause water leak, electric 

  shock, or fire. Ask your dealer or qualified person.

Before electric wiring

CAUTION

The wiring must be securely done by using proper cable. The wires should 
be connected to the terminals not to have external force of the cable.

Faulty connections can cause heat or fire.

The terminal cover (panel) of the unit must be installed securely.

Faulty installation can cause fire or electric shock by dust or water.

The electric installation must be done by qualified person in accordance 
with this installation manual.  Use the separate circuit only for this machine 
and use rated voltage and circuit breaker.

If the electric circuit power is not sufficient or the wiring is not properly 

  done, it can cause electric shock or fire.

Without a circuit breaker, it can cause electric shock.

Install a circuit breaker depending upon the location.

Use standard wires which meet current capacity.

Otherwise, it can cause short-circuit, heat, or fire.

Wires must not have tension.

It can cause snipping, heat, or fire.

Put ground wire.

Never ground to gas pipe, water pipe, lightning conductor, or telephone 

ground wire.  
Faulty ground can cause electric shock.

Before test operation

Turn the power on 12 hours or more before operation.

If you start operation as soon as the power on, it can cause failure.  

  Never turn the power off during season.

Never operate the machine without panel or guard off.

It can cause serious injury being caught by rotating part or burn or 

  electric shock by high voltage part.

Never operate the machine without air filter off.

It can cause failure by dust.

Never operate the switches with your hand wet.

It can cause electric shock.

Never touch refrigerant pipes while the machine running.

The refrigerant pipes becomes high and low temperature while the 

  machine running. If you touch the pipes by hand, it can cause chilblain
  or burn.

Never turn the power off as soon as the machine stops.

Wait for 5 minutes or more.  It can cause water leak or failure.

CAUTION

For models in which this component is used, see the separate sheet.

Содержание PAC-SJ95MA-E

Страница 1: ...ted to the terminals not to have external force of the cable Faulty connections can cause heat or fire The terminal cover panel of the unit must be installed securely Faulty installation can cause fire or electric shock by dust or water The electric installation must be done by qualified person in accordance with this installation manual Use the separate circuit only for this machine and use rated...

Страница 2: ...shield Ground at only one point then no circuit is created and no noise gets in 2 In case that the outdoor unit is grounded connect the ground wire supplied as accessory to the S terminal secondary of M NET terminal block and M NET ground terminal inside of electric box with using screws supplied 2 Attention for M NET connection Pay attention to the next points for wiring of shielded wires CAUTION...

Страница 3: ...ength 680 mm 27 inch Length 480 mm 19 inch Length 280 mm 11 inch Color White Length 380 mm 15 inch Color Red Lead wire A 5 wires Lead wire B 5 wires Wire Marking INV type Always make sure that the markings and the applicable model match If used incorrectly parts could be damaged Wire Marking NON INV Always make sure that the markings and the applicable model match If used incorrectly parts could b...

Страница 4: ...n the switch OFF when MA remote controller or wireless remote controller is NOT connected to indoor unit Note SW1 3 is always ON M NET board SW1 8 ON Outdoor unit M NET board SW1 8 OFF Outdoor unit Indoor unit RC OR MA MA MA remote controller RC Wireless remote controller Indoor unit Centralized controller Centralized controller FUNCTION Set the connection of MA remote controller or wireless remot...

Страница 5: ...onnect CN5 of M NET board connection and CNMNT of outdoor control board Caution Wire Marking INV type Connector color Red Always make sure that the markings and the applicable model match If used incorrectly parts could be damaged Use lead wire C to connect CND of M NET board connection and CNVMNT of outdoor control board Use lead wire D to connect CN2M of M NET board connection and terminals A an...

Страница 6: ...te label under terminal block Use lead wire A to connect CN5 of M NET board connection and CNMNT of outdoor control board Caution Wire Marking INV type Connector color Red Always make sure that the markings and the applicable model match If used incorrectly parts could be damaged Use lead wire C to connect CND of M NET board connection and CNVMNT of outdoor control board Use lead wire D to connect...

Страница 7: ...page 2 Note2 Take great care that no lead wire is caught on anything when installing panels Terminal block M NET Terminal screw M3 20 Ground wire and screw M4 8 Label M NET Board Screws M4o8 Plate2 Control board Install M NET board with insulation sheets and supports on the plate2 so that the rotary switches SW11 SW12 right side at the four points indicated by arrows Note Push it firmly until you ...

Страница 8: ...olor White Always make sure that the markings and the applicable model match If used incorrectly parts could be damaged Use lead wire C to connect CND of M NET board connection and CNVMNT of outdoor control board Use lead wire D to connect CN2M of M NET board connection and terminals A and B of terminal block Polarity is not a concern Note Connect the wire firmly making sure that the screws on ter...

Страница 9: ...Use lead wire D to connect CN2M of M NET board connection and terminals A and B of terminal block Polarity is not a concern Note Connect the wire firmly making sure that the screws on terminal block are not loose The lead wires should be tied together with the other lead wires with the fastener not to loose Wiring length is adjusted according to apparatus Note1 Use ground wire and screw as require...

Страница 10: ... page 2 Note2 Take great care that no lead wire is caught on anything when installing panels Terminal block M NET Terminal screw M3o20 Ground wire and screw M4o8 Label M NET Board Screws M4o8 Plate3 Control board Install M NET board with insulation sheets and supports on the plate3 so that the rotary switches SW11 SW12 faces up at the four points indicated by arrows Note Push it firmly until you h...

Страница 11: ... NET board connection and CNVMNT of outdoor control board Use lead wire D to connect CN2M of M NET board connection and terminals A and B of terminal block Polarity is not a concern Note Connect the wire firmly making sure that the screws on terminal block are not loose The lead wires should be tied together with the other lead wires with the fastener not to loose Wiring length is adjusted accordi...

Страница 12: ...HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Отзывы: