2

Centralized

controller

L1

L2

L3

Power supply

unit

M-NET transmission line

(Centralized control line)

M-NET transmission line

(Indoor control line)

A transmission line

MA remote controller line

Maximum power feeding length for 
the centralized control line:
L1         

[

 200 m (656 ft)

L2 + L3 

[

 200 m (656 ft)

Indoor unit

Indoor unit

Indoor unit

Indoor unit

ME

controller

MA

controller

M-NET

Outdoor

unit

Mr. SLIM

Outdoor

unit

M-NET

Adapter

Indoor unit

Bad example (Multiple ground of shielded wire)

(1) Ground wire connection

(2) Length of M-NET transmission line

Centralized
controller

Power supply
unit

Outdoor
unit (*1)

Outdoor
unit (*1)

M-NET transmit wire

NO

NO

NO

Centralized
controller

Power supply
unit

Outdoor
unit (*1)

Outdoor
unit (*1)

M-NET transmit wire

OK

Centralized
controller

Power supply
unit

Outdoor
unit (*1)

Outdoor
unit (*1)

M-NET transmit wire

OK (*2)

Good example (One spot ground of shielded wire)

Good example (One spot ground of shielded wire)

(*1) Refer to the appendix List of Models to check the applicable models.

Note: If the shield and earth are grounded in two or more locations, electrical circuit is generated through them, and a 

potential difference is created because of the impedance difference between or among the ground locations. 
This may cause noise in the shield. Ground at only one point, then no circuit is created and no noise gets in.

(*2) In case that the outdoor unit is grounded, connect the ground wire supplied as accessory to the S terminal (secondary)  

of M-NET terminal block and M-NET ground terminal inside of electric box with using screws supplied.

(*2)

Attention for M-NET connection

Pay attention to the next points for wiring of shielded wires.

CAUTION

The shielded wires of M-NET transmission should be
connected with the ground wire at any only one place
of the unit to be connected.

• It can cause the transmission error due to noise.

Outdoor unit digital LED display reads "Ed" "A7" error.
Centralized controller reads “0403” “6607” error.

CAUTION

The shielded wires of M-NET transmission should be 
used below the maximum line length.

• It can cause the transmission error.

Outdoor unit digital LED display reads "Ed" "A7" error.
Centralized controller reads "0403" "6607" error.

M-NET
terminal block

Ground wire

(accessory)

Transmit
wire

Shielded
wire

(3) Using dual set point

1. To activate dual set point, make sure that all units and controllers in one group have dual set point function.
2. To change the temperature display setting of existing group from single to dual set point, make sure to restart the 

whole system related.

3. When ME remote controller is included in same group in the case of 2, make sure to initialize* ME remote controller 

before use.
(*Refer to the ME remote controller installation manual. <Service Menu.>)

Содержание PAC-SJ95MA-E

Страница 1: ...ted to the terminals not to have external force of the cable Faulty connections can cause heat or fire The terminal cover panel of the unit must be installed securely Faulty installation can cause fire or electric shock by dust or water The electric installation must be done by qualified person in accordance with this installation manual Use the separate circuit only for this machine and use rated...

Страница 2: ...shield Ground at only one point then no circuit is created and no noise gets in 2 In case that the outdoor unit is grounded connect the ground wire supplied as accessory to the S terminal secondary of M NET terminal block and M NET ground terminal inside of electric box with using screws supplied 2 Attention for M NET connection Pay attention to the next points for wiring of shielded wires CAUTION...

Страница 3: ...ength 680 mm 27 inch Length 480 mm 19 inch Length 280 mm 11 inch Color White Length 380 mm 15 inch Color Red Lead wire A 5 wires Lead wire B 5 wires Wire Marking INV type Always make sure that the markings and the applicable model match If used incorrectly parts could be damaged Wire Marking NON INV Always make sure that the markings and the applicable model match If used incorrectly parts could b...

Страница 4: ...n the switch OFF when MA remote controller or wireless remote controller is NOT connected to indoor unit Note SW1 3 is always ON M NET board SW1 8 ON Outdoor unit M NET board SW1 8 OFF Outdoor unit Indoor unit RC OR MA MA MA remote controller RC Wireless remote controller Indoor unit Centralized controller Centralized controller FUNCTION Set the connection of MA remote controller or wireless remot...

Страница 5: ...onnect CN5 of M NET board connection and CNMNT of outdoor control board Caution Wire Marking INV type Connector color Red Always make sure that the markings and the applicable model match If used incorrectly parts could be damaged Use lead wire C to connect CND of M NET board connection and CNVMNT of outdoor control board Use lead wire D to connect CN2M of M NET board connection and terminals A an...

Страница 6: ...te label under terminal block Use lead wire A to connect CN5 of M NET board connection and CNMNT of outdoor control board Caution Wire Marking INV type Connector color Red Always make sure that the markings and the applicable model match If used incorrectly parts could be damaged Use lead wire C to connect CND of M NET board connection and CNVMNT of outdoor control board Use lead wire D to connect...

Страница 7: ...page 2 Note2 Take great care that no lead wire is caught on anything when installing panels Terminal block M NET Terminal screw M3 20 Ground wire and screw M4 8 Label M NET Board Screws M4o8 Plate2 Control board Install M NET board with insulation sheets and supports on the plate2 so that the rotary switches SW11 SW12 right side at the four points indicated by arrows Note Push it firmly until you ...

Страница 8: ...olor White Always make sure that the markings and the applicable model match If used incorrectly parts could be damaged Use lead wire C to connect CND of M NET board connection and CNVMNT of outdoor control board Use lead wire D to connect CN2M of M NET board connection and terminals A and B of terminal block Polarity is not a concern Note Connect the wire firmly making sure that the screws on ter...

Страница 9: ...Use lead wire D to connect CN2M of M NET board connection and terminals A and B of terminal block Polarity is not a concern Note Connect the wire firmly making sure that the screws on terminal block are not loose The lead wires should be tied together with the other lead wires with the fastener not to loose Wiring length is adjusted according to apparatus Note1 Use ground wire and screw as require...

Страница 10: ... page 2 Note2 Take great care that no lead wire is caught on anything when installing panels Terminal block M NET Terminal screw M3o20 Ground wire and screw M4o8 Label M NET Board Screws M4o8 Plate3 Control board Install M NET board with insulation sheets and supports on the plate3 so that the rotary switches SW11 SW12 faces up at the four points indicated by arrows Note Push it firmly until you h...

Страница 11: ... NET board connection and CNVMNT of outdoor control board Use lead wire D to connect CN2M of M NET board connection and terminals A and B of terminal block Polarity is not a concern Note Connect the wire firmly making sure that the screws on terminal block are not loose The lead wires should be tied together with the other lead wires with the fastener not to loose Wiring length is adjusted accordi...

Страница 12: ...HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Отзывы: