7
3.Installation procedure [Applicable model : Group C]
Attach the plate2 , using two screws .
Use lead wire-C to connect CND of
M-NET board connection and CNVMNT
of outdoor control board.
Use lead wire-D to connect CN2M of
M-NET board connection and terminals
A and B of terminal block Polarity is not a
concern.
Note:
Connect the wire firmly making sure that the
screws on terminal block are not loose.
The lead wires should be tied together with
the other lead wires with the fastener
not to loose.
Wiring length is adjusted according to
apparatus.
Note1:
Use ground wire and screw as required
to connect the shield of M-NET transmission
line to the unit.
(See the attention on page 2)
Note2:
Take great care that no lead wire is caught
on anything when installing panels.
Terminal block (M-NET)
Terminal screw (M3×20)
Ground wire
and screw (M4×8)
Label
M-NET Board
Screws (M4
o
8)
Plate2
Control board
Install M-NET board (with insulation
sheets and supports) on the plate2 so
that the rotary switches (SW11, SW12) right
side (at the four points indicated by arrows).
Note: Push it firmly until you hear it “click”.
Use terminal screw to secure terminal
block .
Note:
Terminal block has a round boss for
positioning: Fit the round boss into the
positioning hole in steel-plate.
Use lead wire-A to connect CN5 of
M-NET board connection and CNMNT of
outdoor control board.
• Caution
Wire Marking: INV type,
Connector color: Red
Always make sure that the markings and
the applicable model match. If used
incorrectly, parts could be damaged.
Lead wire-D
Paste label under terminal block .