82
4. Parameter description
Parameter
4.25 Restart Function (P.57, P.58, P.150, P.160)
P.57 “Restart coasting time”
P.58 “Restart cushion time”
P.150 “Restart mode selection”
P.160 “Stall prevention operation level when restart”
Parameter
Factory setting
Setting range
Remarks
57
9999
0~30s
,
9999
9999: restart function invalid
58
10s
0~60s
---
150
0
0~221
---
160
120%
0~200%
When restart, stall prevention
operation level
<Setting>
• When the motor is running, once the driving power is interrupted, the output voltage will not be
output instantly. When the power is recovered, if P.57=9999, the inverter will not restart
automatically, and if P.57=0.1~5, the motor coasts for a while (the set value of P.57), then the
inverter will restart the motor automatically.
• Once the motor was automatically restarted, the output frequency of the inverter is the target
frequency, but the output voltage is zero. Then the voltage will be increased gradually to the
expected voltage value. The period for voltage increasing is called ‘Restart cushion time (P.58)’.
Instantaneous (power failure) time
Power supply
(R/L1
,
S/L2
,
T/L3)
Motor speed N
(r/min)
Inverter output
frequency f (Hz)
Inverter output
voltage E (v)
Restart cushion time
P.58 setting
Coasting time
P.57setting
*
* The output shut off timing differs
according to the load condtion
• There are 4 digits in P.150, every digit have the different meaning, relevant positions as following:
P. 150 =
0
:
No frequency search
1
:
Immediate frequency search
2
:
Cheapen voltage
0
:
One electrify
1
:
Every starting
2
:
Stop momentary
0
:
No detection of rotation
1
:
The detection of rotation
2
:
P.78=0
,
The direction of rotation
P.78=1
,
2 No direction of rotation