108
4. Parameter description
Parameter
P.195
P.194
Value A
Value B Singal across
terminal 2-5
R
u
n
n
in
g
f
re
q
u
en
cy
s
et
v
al
u
e
Note: 1. The equation for the above curve is:
Running frequency-P.194
Voltage value-Value A
P.195-P.194
Value B-Value A
=
2. If the user can not provide the actual stability of the signal input, you can manually set the parameters
P.192 and P.193. The value of P.192 corresponds to the frequency which P.194 set. The value of P.193
corresponds to the frequency which P.195 set. When set the parameters manually, make sure the range of
P.194 and P.195, and then adjust the voltage value of P.192 and P.193.
3. After any of P.192~P.195 is reset, the curve of P.38 is invalid.
4. If P.187=1, P.194 is in the range of 0~600Hz, P.195 is in the range of 0~1000Hz.
4.54 Input Signal across Terminal 4-5 (P.196~P.199)
P.196“Frequency corresponds to the
minimum input current/voltage across
terminal 4-5”
P.197“Frequency corresponds to the
maximum input current/voltage across
terminal 4-5”
P.198“Minimum input current/voltage
across terminal 4-5”
P.199“Maximum input current/voltage
across terminal 4-5”
Related parameters
P.80~P.84 , P.86
“
Multi-function terminals selection
”
P. 189
“
Factory setting function
”
Parameter
Factory setting
Setting range
Remarks
196
0 Hz
0~60Hz(Note5)
---
197
50Hz
0~400Hz(Note5)
P.189=1
60Hz
P.189=0
198
0
0~20
---
199
0
0~20
---
<Setting>