102
4. Parameter description
Parameter
Parameter
Factory
setting
Setting
range
Remarks
160
0
0~5
4
When in ‘monitoring output voltage’ mode, the screen will
display the value of the input signal across terminal 4-5
(mA/V).
5
When in ‘monitoring output voltage’ mode, the screen will
display the current thermal accumulating record for inverter.
4.48 PID Control (P.170~P.183)
P.170 “PID function selection”
P.172 “PID proportion Gain ”
P.171 “PID feedback control method
selection”
P.173 “PID integration Gain ”
P.174 “PID differential Gain”
P.175 “Abnormal deviation level”
P.176 “Exception duration time”
P.177 “Exception handling mode”
P.178 “Sleep
detects
deviation”
P.179 “ Sleep
detects
duration time”
P.180 “Revival level”
P.181 “Outage level”
P.182 “Integral upper limit frequency”
P.183 “Deceleration step length with stable pressure”
● During the operation of PID control, the frequency displayed on the screen is the output frequency
of the inverter.
● The function of Stall Prevention operates according to the setting frequency before PID control.
Please pay attention to the Gain setting during the process of PID Gain setting in case that the
output current can not be limited absolutely.
● Under PID control, the output frequency is also limited between maximum frequency and
minimum frequency.
● Please refer to the instructions of P.60 about the input signal filter on terminal 4-5 and terminal 2-5.
● The sketch map of PID function is as follows:
s
T
:
Sampling period
=
10ms
Parameter
Factory setting
Setting range
Remarks
170
0
0
,
1
,
2
0
When P.170 = 0, PID is forbidden
1
When P.170 = 1, the feedback value is set
by voltage which is from terminal 2-5
2
When P.170 = 2, the feedback value is set
by current which is from terminal 4-5
171
100%
0~1000%
---