56
4. Parameter description
Parameter
4.17 Communication Function (P.32, P.33, P.36, P.48~P.53, P.153~P.154)
P.32 “Serial communication baud rate selection”
P.33 “Communication protocol selection”
P.36 “Inverter station number”
P.48 “Data length”
P.49 “STOP bit length”
P.50 “Parity check selection”
P.51 “CR & LF selection”
P.52 “Number of communication retries”
P.53 “Communication check time interval”
P.153 “Communication error handling”
P.154 “Modbus communication data format”
● When the communication parameters are revised, please reset the inverter.
● The SE2-type inverters have two communication protocols to select, Shihlin protocol and Modbus
protocol. If the communication expansion board is selected, the corresponding communication
protocol is provided. P.32, P.36, P.52, P.53, and P.153 are applied to both of the protocols.
P.48~P.51 is only applied to the Shihlin protocol and P.154 is only applied to the Modbus protocol.
● Continuous communication, please make the following listed parameters set correctly, otherwise it
will not carry out normal continuous communication.
Parameter
Factory
setting
Setting range
Remarks
32
1
0~2
0
Baud rate: 4800bps
1
Baud rate: 9600bps
2
Baud rate: 19200bps
33
1
0, 1
0
Modbus protocol
1
Shihlin protocol
36
0
0~254
(Note 1)
48
0
0, 1
0
Data length: 8 bit
1
Data length: 7bit
49
0
0~1
0
STOP bit length: 1 bit
1
STOP bit length: 2 bit
50
0
0~2
0
Not Given
1
odd
2
even