84
Byp Fan Time
Reset
Reset timing of bypass fans.
85
Battery Over
Temp.
Battery is over temperature. It’s optional.
86
Bypass Fan
Expired
Working life of bypass fans is expired, and it’s
recommended that the fans are replaced with new fans. It
must be activated via software.
87
Capacitor
Expired
Working life of capacitors is expired, and it’s recommended
that the capacitors are replaced with new capacitors. It must
be activated via software.
88
Fan Expired
Working life of power modules’ fans is expired, and it’s
recommended that the fans are replaced with new fans. It
must be activated via software.
89
INV IGBT Driver
Block
Inverter IGBTs are shutdown.
Please check if power modules are inserted in cabinet
correctly.
Please check if fuses between rectifier and inverter are
broken.
90
Battery Expired
Working life of batteries is expired, and it’s recommended
that the batteries are replaced with new batteries. It must
be activated via software.
91
Bypass CAN Fail
The CAN bus between bypass module and cabinet is
abnormal.
92
Dust Filter
Expired
Dust filter need to be clear or replaced with a new one
102
Wave Trigger
Waveform has been saved while UPS fail
103
Bypass CAN Fail
Bypass and cabinet communicate with each other via CAN
bus. Check
If connector or signal cable is abnormal.
If monitoring board is abnormal.
105
Firmware Error
Manufacturer used only.
106
System Setting
Error
Manufacturer used only.
107
Bypass Over
Temp.
Bypass module is over temperature. Please check
If bypass load is overload
If ambient temperature is over 40°C
If bypass SCRs are assembled correctly
If bypass fans are normal
108
Module ID
Duplicate
At least two modules are set as same ID on the power
connector board, please set the ID as correct sequence
o
Note
Different colors of the words represent different level of events:
(a)Green, an event occurs
;
(b)Grey, the event occurs then clears
;
(c)Yellow, warning occurs
;