42 Shield T3 60 – 500KVA User Manual
3
Operator Control and Display Panel
3.1
UPS operator panel
The structure of operator control and display panel for cabinet is shown in
1
2
3
4
6
7
8
9
5
BYP
INV
MUTE
10
11
12
1: LCD touch screen 2: EPO switch 3: Audible Alarm (Buzzer)
4: Status indicator 5: Bypass indicator 6: Rectifier indicator
7: Inverter indicator 8: Load indicator 9: Battery indicator
10: Bypass transfer 11: Inverter transfer 12: Mute
Figure3-1
Control and display panel
The LCD panel for cabinet is divided into three functional areas: LED indicator, control
and operation keys and LCD touch screen.
3.1.1
LED Indicator
There are 6 LEDs on the panel to indicate the operating status and fault. (See Figure 4-
1).The description of indicators is shown in Table 3-1
Table 3-1
Status description of indicator
Indicator
State
Description
Rectifier
indicator
Steady
green
Rectifier normal for all modules
Flashing
green
Rectifier normal for at least one module, mains normal
Steady red
Rectifier fault
Flashing red Mains abnormal for at least one module
Off
Rectifier not operating
Battery
indicator
Steady
green
Battery charging
Flashing
green
Battery discharging