Shield T3 60 – 500KVA User Manual
31
o
Note
The recommended cable section for power cables are only for situations described
below
:
Ambient temperature
:
30
℃
.
AC loss less than 3%
,
DC loss less than 1%
,
The length of the AC power cables
are no longer than 50 m and the length of the DC power cables are no longer
than 30 m.
Currents listed in the table are based on the 380V system (Line-to-line voltage).
The size of neutral lines should be 1.5~1.7 times the value listed above when the
predominant load is non-linear.
2.6.2
Specifications for Power Cables Terminal
Specifications for power cables connector are listed as
Table 2-3 Requirements for power module terminal
Type
Port
Connection
Bolt
Torque
Moment
60kVA
Mains input
Cables crimped OT
terminal
M6
4.9Nm
Bypass Input
Cables crimped OT
terminal
M6
4.9Nm
Battery Input
Cables crimped OT
terminal
M6
4.9Nm
Output
Cables crimped OT
terminal
M6
4.9Nm
PE
Cables crimped OT
terminal
M6
4.9Nm
90kVA
120kVA
Mains input
Cables crimped OT
terminal
M6
4.9Nm
Bypass Input
Cables crimped OT
terminal
M6
4.9Nm
Battery Input
Cables crimped OT
terminal
M6
4.9Nm
Output
Cables crimped OT
terminal
M6
4.9Nm
PE
Cables crimped OT
terminal
M6
4.9Nm
80kVA
100kVA
Mains input
Cables crimped OT
terminal
M6
4.9Nm
Bypass Input
Cables crimped OT
terminal
M6
4.9Nm
Battery Input
Cables crimped OT
terminal
M8
13Nm
Output
Cables crimped OT
terminal
M6
4.9Nm
PE
Cables crimped OT
terminal
M6
4.9Nm