Page 14
4.2 Use of input terminals
4.2.1 Input terminals on the master control board
Fig.4.1.1 Input Terminals on the Master Control Board
Purposes of the input terminals on the master control board:
No.
Purpose
16
+24VK
17
Input of the MANUAL RELEASE button
18
Input of the MANUAL FIRE ALARM button
19
Input of the PAUSE switch
20
Input of the MANUAL/AUTO switch
21
Input of the MUTE button
22
Input of the RESET button
23
Pressure feedback input terminal for release confirmation
24
Input terminal for agent drop alarm
25
Input terminal of the second detection and alarm circuit
26
Input terminal of the first detection and alarm circuit
Note: It is not allowed to share the input circuit ground and the output circuit ground. The +24V
PGND has been connected with the output circuit ground in the control board.
4.2.2 Connection modes of input terminals
The local input signals include three kinds, namely that for the AGND short/open circuit switch, that for
the +24V short/open circuit switch and that for the detector circuits. The connection modes of the input
signals of different kinds are given in the table below.
Connection
mode
Signal form
of the input
circuit
Connection mode A of the input
circuit (without open circuit fault
detection)
Connection mode B of the input circuit (with
open circuit fault detection)
Applicable
terminal
1
For the
AGND
short/open
circuit
switch
Terminal
19
Terminal
20
Terminal
21
Terminal
22
Terminal
23
Terminal
24
2
For the
+24V
Short/open
circuit
switch
Terminal
17
Terminal
18
3
Detector
circuits
Terminal
25
Terminal
26
Содержание JB-QBL-QM200
Страница 1: ...1 JB QBL QM200 Fire Alarm Control Panel Agent Releasing Control Panel...
Страница 10: ...Page 7 Fig 2 7 Wiring Diagram of the Fire Alarm Controller Active Output...
Страница 11: ...Page 8 Fig 2 8 Wiring Diagram of the Fire Alarm Controller Partial Passive Output...
Страница 16: ...Page 13 Fig 4 1 Terminal Positions...