SHENZHEN FANHAI SANJIANG ELECTRONICS JB-QBL-QM200 Скачать руководство пользователя страница 21

Page 18

loads at the ends of the circuit. The isolation diodes in the diagrams are used for the short or open circuit
fault detection voltage, but they will not affect the output of driving signals. The selection of isolation
diodes should depend on the load current value. For example, IN5401 isolation diodes should be used
for the driving circuits of the electromagnetic valves (load current: 1~3A).

4.3.2 Description of the output terminals on the master control board

Fig. 4.1 Output Terminals on the Master Control Board

Terminal description:

1.

Terminal 1 on the master control board:

It is for +24V DC power output.(

To connect the

terminal MANUAL FIRE ALARM button 2

)

1)

The +24V power supply necessary to the input terminals of the system is led out from terminal 1.

2)

It can be connected to external devices as a +24V power supply .

2.

Terminal 2 on the master control board: I

t is for the output of electromagnetic valve driving

signals and for the +24V active output.

1)

In any of the following three circumstances, the system will start the electromagnetic valves.

No.

State description

Remarks

1

The system is in the auto mode, the detector has detected a
compound fire alarm and the set delay time is reached.

2

The EMERGENCY RELEASE button on the panel is pressed and
the set delay time is reached.

3

The EXTERNAL MANUAL RELEASE button is pressed and the set
delay time is reached.

2)

Electromagnetic valves are inductive loads, it is therefore necessary to select between the two
connection modes of category 2. Select connection mode A or B according to the judgment on
whether the output circuit has a short or open circuit fault detection function.

When the output circuit needs no short or open circuit fault detection function, select
connection mode A and set the jumper JP7 on the master control board to the ON position.
See Table 3.1.2.

When the output circuit needs a short or open circuit fault detection function, select connection
mode B and set the jumper JP7 on the master control board to the OFF position.

3)

When the circuit suffers a fault, the outputs driven by the electromagnetic valves due to a compound
fire alarm will be forbidden even if the compound fire alarm is detected by the detectors. The
EMERGENCY RELEASE button can still work at this time.

3.

Terminal 3 on the master control board:

It is for the output of release indication signals and for

the +24V active output.

1)

The specific connection mode should be selected according to the load characteristics and the

judgment on whether the output circuit has a short or open circuit fault detection function.

When the connection mode with a short or open circuit fault detection function is selected, the
jumper JP1 on the master control board should be set to the OFF position.

When connection mode without a short or open circuit fault detection function is selected, the
jumper JP1 on the master control board should be set to the ON position. See Table 3.1.2.

When the said fault is occurring, the system will report an output fault (the output fault indicator
on the display panel will be lit).

2)

The maximum output current is 1A.

3)

In case of an input of an external pressure feedback signal or an operation of the electromagnetic
valves, terminal 3 will output a +24V voltage.

4.

Terminal 4 on the master control board: I

t is used as a passive output terminal of fault output.

The jumper JP10 on the master control board is off and terminals 4 and 5 form normally open
passive dry contacts as the passive output signals of fault output. The maximum output current is
1A.

5.

Terminal 5 on the master control board:

It is for the output of faults.

1)

The jumper JP10 on the master control board is off and terminals 4 and 5 form normally open
passive dry contacts.

2)

The jumper JP10 on the master control board has a short circuit and terminal 5 is a +24V active
output terminal for faults.

3)

The maximum output current is 1A.

4)

When it is set as +24V active output terminal, the connection mode should be selected according to
the load characteristics and the judgment on whether the output circuit has a short or open circuit
fault detection function.

When the connection mode with a short or open circuit fault detection function is selected, the
jumper JP4 on the master control board should be set to the OFF position. See Table 3.1.2.

When the connection mode without a short or open circuit fault detection function is selected,
the jumper JP4 should be set to the ON position.

Содержание JB-QBL-QM200

Страница 1: ...1 JB QBL QM200 Fire Alarm Control Panel Agent Releasing Control Panel...

Страница 2: ...de of emergency release delay 11 3 1 4 Setup of the delay mode for the EXTERNAL MANUAL RELEASE button 11 3 1 5 Setup of the control mode of the key lock over the EMERGENCY RELEASE button on the displa...

Страница 3: ...ase refer to Chapter V Panel Display and Chapter VI Key On Off Warning It is necessary to dismount all electromagnetic valves electric detonators from the devices which are driven by them during syste...

Страница 4: ...ifications 1 AC input voltage AC 220V 20 50Hz AC input power 120W DC standby power DC24V 7 0Ah consisting of two fully sealed maintenance free DC12V 7 0Ah storage batteries connected in series 2 Outpu...

Страница 5: ...he display panel and displays the start countdown The delay manner of the manual start may also be set by the user through the jumpers on the display panel too 11 It provides an open circuit fault det...

Страница 6: ...N OFF Fig 2 1 Installation Holes of the Case The following requirements should be met during installation of the case There must be a space of at least 1m reserved in front of the case There are cable...

Страница 7: ...ecessary to have the AC supply voltage accessed with the help of a voltage stabilizer with a power of larger than 300W or else the switching power supply may be damaged The standby batteries if fully...

Страница 8: ...ate ground wires The installation and connection of the system should comply with the requirements of national standard Code for the Installation and Acceptance of the Fire Alarm System GB50166 92 Bui...

Страница 9: ...he master control board Single fire alarm active output terminal Note in the access mode above that before the fire alarm controller is delivered the black short wire connected to terminal 19 on the m...

Страница 10: ...Page 7 Fig 2 7 Wiring Diagram of the Fire Alarm Controller Active Output...

Страница 11: ...Page 8 Fig 2 8 Wiring Diagram of the Fire Alarm Controller Partial Passive Output...

Страница 12: ...nal input circuit JP16 Not detect the open fault of the Local Manual Auto signal input circuit JP17 Detect the open fault of the signal input circuit of the detector circuit 2 JP18 Not detect the open...

Страница 13: ...n fault of the stop signal input circuit Detect the open fault of the stop signal input circuit JP21 Not detect the open fault of the manual release signal input circuit Detect the open fault of the m...

Страница 14: ...he emergency release delay The factory default is OFF that is to say the electromagnetic valves will be started after the set delay time is reached All possible settings of the jumper JP5 are given in...

Страница 15: ...h means that the EMERGENCY RELEASE button is not controlled by the key lock All possible settings are given in the table below The EMERGENCY RELEASE button on the display panel is controlled by the ke...

Страница 16: ...Page 13 Fig 4 1 Terminal Positions...

Страница 17: ...ut circuit ground and the output circuit ground The 24V PGND has been connected with the output circuit ground in the control board 4 2 2 Connection modes of input terminals The local input signals in...

Страница 18: ...an open circuit fault detection function is selected the jumper JP20 on the master control board should be set to the ON position as shown in Table 3 1 2 and Fig 4 1 and the built in termination resi...

Страница 19: ...s in the control board should not be used and a 10K termination resistor should be arranged at the end of the circuit shown in connection mode B 2 A short circuit of the switch suggests a reset status...

Страница 20: ...ly The connection modes of passive output circuits are related to the actual use and will not be introduced here Connection modes of the output circuits Connecti on mode Type of load Connection mode A...

Страница 21: ...re alarm will be forbidden even if the compound fire alarm is detected by the detectors The EMERGENCY RELEASE button can still work at this time 3 Terminal 3 on the master control board It is for the...

Страница 22: ...t on whether the output circuit has a short or open circuit fault detection function When the connection mode with a short or open circuit fault detection function is selected the jumper JP6 on the ma...

Страница 23: ...T ZONE 2 RELEASE HORN STROBE FAULT MANUAL AUTO RELEASE DELAY RELEASE START RELEASE CONFIRM PANEL MUTE DISPLAY TEST ALARM BELL RESET DELAY STOP QUERY QUERY TIME KEY ON OFF Fig 5 1 Schematic Diagram of...

Страница 24: ...ator light will be lit RELEASE After the system has entered the release status and the electromagnetic valves have been started this indicator light will be lit HORN STROBE FAULT After a short or open...

Страница 25: ...M BELL After the alarm bell is started this indicator light will be lit DELAY STOP After the DELAY STOP button is pressed when the system is in the countdown for release the delay process will be stop...

Страница 26: ...ted the HORN STROBE START indicator close to this key will be lit ALARM BELLIf this key is pressed after the key lock is unlocked the alarm bell may be started or stopped After the alarm bell is start...

Страница 27: ...and both the QUERY indicator and the indicator of the queried content will flash If QUERY TIME is pressed the upper nixie tube will display the year month day and code of the information If QUERY is p...

Страница 28: ...in the format of After BWD key S10 is pressed the figure displayed by the nixie tube will increase within the range of 1 60 in a cyclic way 2 If Switching key S12 is pressed again the nixie tube will...

Отзывы: