Page 24
If
QUERY
is pressed in the monitoring status, the system will enter the selection of types of historical
records for query (including fire alarm, fault and release) and the “Query” indicator will be lit. The first
digit of the lower nixie tube on the display panel (close to the EMERGENCY RELEASE button) refers to
the type. If it displays as
, it means it will query the fire alarm information; if
QUERY
is pressed
again and
is displayed, it means it will query the fault information; if
QUERY
is pressed for the
third time and
is displayed, it means it will query the release information. If
QUERY
is pressed
after that, the system will return to the fire alarm query status and
will be displayed. Press
QUERY TIME
to enter the information display interface of the corresponding type. The lower nixie tube
displays the fault No. (0-999). The content initially displayed refers to the latest information which is the
amount of the information as well. The LED on the display panel indicates corresponding information (air
release, fire alarm or fault). The upper nixie tube displays the time. The content initially displayed is the
specific year in the format of
??
. If
QUERY TIME
is pressed, month/day information in the format
of
? ?
.
? ?
will be displayed. If
QUERY TIME
is pressed again, the hour/minute information in the
format of
??
:
??
will be displayed. If it is pressed for the third time, the code information in the format
of
-
??
-
will be displayed. If it is pressed for the fourth time, the specific year will be displayed again. At
this time, if
QUERY
is pressed and the number displayed by the lower nixie tube is decreased by 1, the
information recorded at earlier time will be displayed.
If
QUERY
is pressed under the alarm status, the system will query the current information and both the
QUERY indicator and the indicator of the queried content will flash. If
QUERY TIME
is pressed, the
upper nixie tube will display the year, month, day and code of the information. If
QUERY
is pressed
again, another piece of information will be displayed.
The meanings of the information codes:
Valve operations: 1. Standby
2. Delay release through the EXTERNAL button
3. Release through the
EMERGENCY RELEASE button on the display panel
4. Release through the probe
Alarms: 5. Manual alarm
6. Standby
7. Alarm of circuit 1. 8. Alarm of circuit 2
Faults: 9. Release fault
10. Input fault
11. Output fault
12. AC fault
13. DC fault
14. agent drop
15. Fault of circuit 1
16. Fault of circuit 2
17. DC lack
18. AC lack
19. MCP fault
20.
Audible/visual alarm fault
21. Sounder fault
Release: 22. Start time of the EMERGENCY RELEASE button on the display panel
23. Start time of compound fire alarm
24. Start time of external manual release
25. Release
confirmation time
Note: The system will record information by type. It can record 2997 items in all, including 999 items of
fire alarm information, fault information and release information. If the number of each type of information
is more than 999, the earliest information will be covered.
QUERY TIME
and
KEY ON/OFF
form the key lock. Besides, if used with the
QUERY
key, it can finish
the information query.
Reset
It is a reset key for system software. After it is pressed, the system will cancel all alarm and fault
indications and initialize all outputs.
SYSTEM TEST
It is for system test. During the system test process, the indicators will be lit one by one;
the figure on the clock nixie tube will change from 1 to 9 and the audible alarm will change from fault
sound to fire alarm sound, release the countdown sound and release alarm sounds in order. See Fig.6.1
for the conditions of various alarm sounds.
Fault Sound
F
Sound
ire Alarm
Release
Sound
Countdown
Sound
Mute
Fig.6.1 Schematic Diagram of the Modes of Alarm Sounds
Содержание JB-QBL-QM200
Страница 1: ...1 JB QBL QM200 Fire Alarm Control Panel Agent Releasing Control Panel...
Страница 10: ...Page 7 Fig 2 7 Wiring Diagram of the Fire Alarm Controller Active Output...
Страница 11: ...Page 8 Fig 2 8 Wiring Diagram of the Fire Alarm Controller Partial Passive Output...
Страница 16: ...Page 13 Fig 4 1 Terminal Positions...