13
·
26
13
13-6 Application instruction using instruction system
(1) F-202
F-202
OPCH
F-202
OPCH
PORT
CH·ST
file N
n
Symbol
Specify the target station for inter-PC data communications to be
performed across the satellite net (ZW/JW-20CM). These instructions
are used in conjunction with the F-204 (SEND) or F-205 (RCV)
instructions.
Function
Range of PORT
Range of CH
Range of ST
Range of file N
Range of n
Condition
Flag
Input the port number of rack panel that installed on ZW/JW-20CM.
Example: JW-13BU
0 to 3 : Channel number for the specified port number. Available for use
four times by classifying the same port numbers into CH0, CH1,
CH2, and CH3 in the PC program.
00 to 77
(8)
: Communication target station number. Set by octal.
0 to 7 : Specify the PC data area (file number) of the communication
target station. [
※
]
000000 to 177777
(8)
: Specify the PC data top address (file address) of
the communication target station. [
※
]
When an input signal is ON, keep it ON until the flag is changed.
Refer to F-204 and F-205 for the combination of F-204 and F-205. [
※
]
• After turning ON the input signal of F-202, keep it ON until the finish of the execution of the
instruction. If the input signal is turned OFF during execution of the instruction, the instruction
ends in an incomplete condition. Under this condition, next, when an F-202 instruction is given, it
will come to a “communication jam,” and the instruction will not be executed. Turn the power OFF
and then ON again for recovery.
[
※
] F-202 instructions must always be used in conjunction with the F-204 (SEND) or F-205 (RCV)
instruction.
Open Channel
JW-20CM
Control module
Power module
Port No.
②③④⑤⑥⑦