background image

EN-1

A

B

D

C

Trap

PIPING

Max. piping 

length:A

Max. total piping length of all 

unit

Min. piping 

length:A

Max. height difference:

Chargeless Max. 

piping length

Additional refrigerant

B

C

D

82 ft (25 m)

2 units:164 ft (50 m) 

3 units, 4 units: 230 ft (70 m)

10 ft (3 m)

49 ft 

(15 m)

49 ft 

(15 m)

49 ft 

(15 m)

164 ft (50 m)

0.16 oz/ft (15 g/m)

1. Standard piping length is 25 ft (7.6 m).
2. When the outdoor unit is placed at a higher level than the indoor unit, provide a trap near the hose’s lead-in port. 

Use the refrigerant pipes shown in the table below.

Pipe size

Pipe thickness

Thermal insulation 

Liquid side

1/4" (ø 6.35 mm)

0.03 inch (0.8 mm)

Thickness: 0.24 inch (6 mm) or thicker
Material: Polyethylene foam

Gas side

3/8" (ø 9.52 mm)
1/2" (ø 12.7 mm)

• The thermal insulation should cover both the gas and liquid pipes. 

ACCESSORIES

ITEMS

Q’ty

ITEMS

Q’ty

ITEMS

Q’ty

1

 Installation Manual

1

3

 Drain tray

1

5

 Reducer (1/2"

3/8")

2

2

 Base pan cap

4

4

 Drain joint

1

INSTALLATION DIAGRAM

3.3 ft (1000 

mm) or more

1.3 ft (400 

mm) or more

•  Provide as much installation space as possible for 

effi cient air-conditioning. 

For installation work

1. Place the outdoor unit on a stable base.
2. Provided suffi cient space around the unit. It should also be 

well ventilated.

3. The unit should not be exposed to strong wind nor splashed 

with rain water.

4. Water drain from the unit should be let out without problem. 

Lay a drain hose if required. In cold regions, installation of 
the drain pipe is not advisable as freezing could result.

5. Keep TV sets, Radio and other related electronic appliances 

at least 3.3 feet away from the unit.

6. Avoid locations exposed to machine oil vapor, salty air (facing 

the seashore, for example), hot spring vapor sulfur gas, etc. 
Such location can cause breakdown.

7. Avoid locations exposed to muddy water (along a road, for 

example) or where the unit can be tampered with.

8. Select a location where the outgoing air or operating noise 

cannot annoy others.

9. Keep the air outlet opening free of any obstacle. This could 

affect the performance of the unit and create loud noises.

10.For colder climate areas, install the unit in a location not 

affected by snow or ice falls (example: roof houses). Unit 
should be installed minimum 10 inches (25 cm) from ground 
level or follow your country’s average snowfall accumulation.

Carefully read and follow these instructions for smooth and trouble-free installation.
This manual describes the installation of outdoor unit only
For the installation of the indoor unit, see the installation manual accompanying indoor unit.

SAFETY PRECAUTIONS

• Tighten the fl are nut with a torque wrench according to the 

specifi ed method. 

If the fl are nut is tightened too hard, the fl are nut may be broken after a 
long time and cause refrigerant gas leakage.

• When installing the unit, take care not to enter air substance other 

than the specifi ed refrigerant(R410A) in the refrigerant cycle. 

Otherwise, it will cause burst and injury as a result of abnormal high 
pressure in the refrigerant cycle.

• Be sure to connect the refrigerant pipe before running the 

compressor. 

Otherwise, it will cause burst and injury as a result of abnormal high 
pressure in the refrigerant cycle. 

• Ground the unit. 

Incomplete ground may cause electrical shock.

• Install a Ground Fault Interrupt (GFI) circuit breaker depending on 

the installation location of the unit (such as highly humid areas).

 

If GFI breaker is not installed, it may cause electric shock.

• Arrange the drain hose to ensure smooth drainage.

Insuffi cient drainage may cause wetting of the room, furniture etc.

• This room air conditioner uses refrigerant R410A.

Use the pipe, fl are nut and tools exclusively for R410A.

NOTES ON LOCATIONS

 

1 ft (300 

mm) 

or more

• Installation must be made in accordance with the installation 

manual by qualifi ed service personnel. 

Incorrect work will cause electric shock, water leak, fi re.

• Be sure to use the attached accessories parts and specifi ed 

parts for installation.

Use of other parts will cause electric shock, water leak, fi re, the unit 
falling.

• The appliance shall be installed and wired in accordance with 

National Electrical Code and by qualifi ed personnel only.

Wrong connection can cause overheating or fi re.

• After installation has complete, check that there is no leakage 

of refrigerant gas.

If the refrigerant gas contact with fi re, it may generate toxic gas.

• Ventilate the room if refrigerant gas leaks during installation.

If the refrigerant gas contact with fi re, it may generate toxic gas.

• Use the specifi ed electrical cable.

Make sure the cable is secured in place and that the terminals are 
free of any excess force from the cable. Otherwise overheating or 
fi re may result.

• Form the cable so that the control box cover, the cord holder 

and cable holder are not loose. 

Otherwise overheating, fi re or electric shock may result.

Coating tape 

(Commercially available) 

Joint

Seal Ring

Flare nut

ENGLISH

1 ft (300 

mm) or more

IM_A3AEX4M3PU(B434)_EN+FR+ES.indb   EN-1

IM_A3AEX4M3PU(B434)_EN+FR+ES.indb   EN-1

2/7/13   11:05:27 AM

2/7/13   11:05:27 AM

Содержание AE-X4M30PU

Страница 1: ...EUR INDIVIDUEL EN DEUX PARTIES MANUEL D INSTALLATION ACONDICIONADOR DE AIRE TIPO SPLIT MANUAL DE INSTALACIÓN OUTDOOR UNIT AE X4M30PU ENGLISH FRANÇAIS ESPAÑOL IM_A3AEX4M3PU B434 _EN FR ES indb 1 IM_A3AEX4M3PU B434 _EN FR ES indb 1 2 7 13 11 05 27 AM 2 7 13 11 05 27 AM ...

Страница 2: ... installation of outdoor unit only For the installation of the indoor unit see the installation manual accompanying indoor unit SAFETY PRECAUTIONS Tighten the flare nut with a torque wrench according to the specified method If the flare nut is tightened too hard the flare nut may be broken after a long time and cause refrigerant gas leakage When installing the unit take care not to enter air subst...

Страница 3: ...ombination it is possible to install 2 units 15 class 18 class 18 class 18 class Joint 1 2 3 8 Seal ring Flare nut 3 8 Outdoor unit Indoor unit PORT SIZE OF THE OUTDOOR UNIT Base pan cap 2 Connecting the pipes Connect the pipes for the indoor unit first and then for the outdoor unit 1 Tighten the flare nuts by hand for the first 3 4 turns 2 Use a spanner and torque wrench to tighten up the pipes D...

Страница 4: ...wrench Close it after 5 second and check for gas leakage 8 Disconnect the gauge manifold hose from the service port 9 Fully open the stop valve liquid side with hexagon wrench Turn all the way up to contact 10 Fully open the stop valve gas side with hexagon wrench Turn all the way up to contact 11 Firmly tighten the service port cap and both valve shaft caps with a torque wrench at the specified t...

Страница 5: ...leted normally all LED will flash simultaneously and the operation will stop Wire check time 10 20 minutes When self correction can not done all LED will indicate triple flash for eight times and the operation will stop Check and correct following points Check all pipings are connected Check the stop valves are open After correction repeat the wire check again If error is still detected or other t...

Страница 6: ...onnect the gauge manifold hose to the service port of the stop valve gas side 2 To start pump down press the PUMP DOWN button SW1 for 5 seconds or more The OPERATION lamp on the indoor unit will flash and three BEEP will be emitted 3 After 5 10 minutes fully close the stop valve liquid side 4 Close the stop valve gas side when the compound gauge reading becomes almost 0 MPa 0 cmHg 5 To stop the pu...

Страница 7: ...ENGLISH EN 6 IM_A3AEX4M3PU B434 _EN FR ES indb EN 6 IM_A3AEX4M3PU B434 _EN FR ES indb EN 6 2 7 13 11 05 33 AM 2 7 13 11 05 33 AM ...

Страница 8: ...éfrigérant R410A Utilisez les tuyaux de réfrigérant l écrou évasé et les outils exclusive ment pour le R410A REMARQUES SUR LES EMPLACEMENTS 300 mm 1 pi ou plus L installation doit être faite en conformité avec le manuel d ins tallation par un technicien professionnel Un travail incorrect peut provoquer un choc électrique une fuite d eau un incendie Assurez vous d utiliser les accessoires et les pi...

Страница 9: ... intérieures Exceptionnellement dans le cas de la combinaison suivante il est possible d installer 2 unités 15 classe 18 classe 18 classe 18 classe Joint 1 2 po 3 8 po Bague d étanchéité Écrou évasé 3 8 po Unité extérieure Unité intérieure DIMENSION DE L ORIFICE DE L UNITÉ EXTÉRIEURE Bouchon du plateau de base 2 Raccordement des tuyaux Raccordez les tuyaux pour l unité intérieure en premier puis c...

Страница 10: ...es et vérifier s il y a des fuites de gaz 8 Débrancher le tuyau du manomètre de l orifice de l entretien 9 Ouvrir complètement la vanne d arrêt coté liquide avec une clé hexagonale Tournez vers le haut jusqu au contact 10 Ouvrir complètement la vanne d arrêt Côté gaz avec une clé hexagonale Tournez vers le haut jusqu au contact 11 Serrez fermement le bouchon de l orifice d entretien et des deux bo...

Страница 11: ...les DEL clignotent simultanément et l opération s arrête Durée de la vérification de fil 10 20 minutes Lorsque la correction automatique ne peut pas se faire toutes les DEL indiqueront clignoteront 3 fois et ce huit fois puis l opération s arrêtera Vérifier et corriger les points suivants Vérifier si tous les tuyaux sont raccordés Vérifier si les vannes d arrêt sont ouvertes Après correction répét...

Страница 12: ... arrêt côté gaz lorsque la mesure du manovacuomètre devient presque 0 MPa 0 cmHg 5 Pour arrêter la récupération du fluide appuyez sur la touche PUMP DOWN SW1 pendant au moins 5 secondes 6 Débrancher le tuyau du manomètre de l orifice de l entretien PROCÉDURE SANS UTILISER LE MANOMÈTRE DE PRESSION 1 Pour commencer la récupération du fluide appuyez sur la touche PUMP DOWN SW1 pendant au moins 5 seco...

Страница 13: ...FR 6 FRANÇAIS IM_A3AEX4M3PU B434 _EN FR ES indb FR 6 IM_A3AEX4M3PU B434 _EN FR ES indb FR 6 2 7 13 11 05 40 AM 2 7 13 11 05 40 AM ...

Страница 14: ... describe solo la instalación de la unidad exterior Para la instalación de la unidad interior vea el manual de instalación que se adjunta con la unidad interior PRECAUCIONES DE SEGURIDAD Ajuste la tuerca cónica con una llave de torsión según el método indicado Si la tuerca cónica está demasiado ajustada podría rajarse o romperse después de un tiempo y producir pérdida de gas refrigerante Cuando in...

Страница 15: ...ción siguiente es posible instalar 2 unidades Clase 15 clase 18 Clase 18 clase 18 Junta 1 2 3 8 Anillo de sellado Tuerca cónica 3 8 Unidad exterior Unidad interior TAMAÑO DE LA ABERTURA DE LA UNIDAD EXTERIOR Tapa para bandeja base 2 Conectar los caños Conecte los caños de la unidad interior primero y luego los de la unidad exterior 1 Ajuste las tuercas a mano las primeras 3 4 vueltas 2 Utilice una...

Страница 16: ...gas 8 Desconecte la manguera del manómetro de la abertura de servicio 9 Abra completamente la válvula de cierre lado del líquido con una llave hexagonal Gírela del todo hasta el contacto 10 Abra completamente la válvula de cierre lado del gas con una llave hexagonal Gírela del todo hasta el contacto 11 Ajuste firmemente la tapa de la abertura de servicio y las dos tapas de los ejes de válvula con ...

Страница 17: ...simultáneamente y el funcionamiento se detendrá Periodo de verificación del alambre 10 20 minutos Cuando la autocorrección no se pueda realizar todos los LED indicarán un triple parpadeo ocho veces y el funcionamiento se detendrá Compruebe y corrija los siguientes puntos Compruebe que todas las cañerías estén conectadas Compruebe que las válvulas de cierre estén abiertas Después de la corrección r...

Страница 18: ...rvicio de la válvula de cierre lado del gas 2 Para poner en marcha la evacuación presione el botón PUMP DOWN SW1 durante 5 segundos o más La luz de FUNCIONAMIENTO de la unidad interior parpadeará y se emitirán tres PITIDOS 3 Tras 5 10 minutos cierre completamente la válvula de cierre lado del líquido 4 Cierre la válvula de cierre lado del gas cuando la lectura del manómetro compuesto sea casi 0 MP...

Страница 19: ...ES 6 ESPAÑOL IM_A3AEX4M3PU B434 _EN FR ES indb ES 6 IM_A3AEX4M3PU B434 _EN FR ES indb ES 6 2 7 13 11 05 47 AM 2 7 13 11 05 47 AM ...

Страница 20: ...Printed in Thailand TINS B434JBRZ 13A TH 1 IM_A3AEX4M3PU B434 _EN FR ES indb ES 7 IM_A3AEX4M3PU B434 _EN FR ES indb ES 7 2 7 13 11 05 47 AM 2 7 13 11 05 47 AM ...

Отзывы: