7.3
Startup MOVIFIT
®
7.3.1
Startup in conjunction with PROFIBUS
1. Check correct connection of MOVIFIT
®
.
2. Set the PROFIBUS address using DIP switch S2 (
Æ
page 13) on the MOVIFIT
®
ABOX. Use DIP switches 1 to 7 to set the PROFIBUS address.
The following table uses address 17 as an example to show how to determine the
DIP switch settings for any bus address:
3. Connect MOVIFIT
®
bus terminating resistors at last bus station.
• If MOVIFIT
®
is located at the end of a PROFIBUS segment, it can only be
connected to the PROFIBUS mains by the incoming PROFIBUS cable.
• To prevent malfunctions in the bus system due to reflections, etc., the PROFIBUS
segment must be terminated using bus terminating resistors at the first and last
physical stations.
57952AXX
[1] Example: Address 17
[2] Switch 8 = reserved
Addresses 1 through 125: valid addresses
Addresses 0, 126, 127:
are not supported
Calculation
Remainder
DIP switch setting
Significance
17 / 2 = 8
1
DIP 1 = ON
1
8 / 2 = 4
0
DIP 2 = OFF
2
4 / 2 = 2
0
DIP 3 = OFF
4
2 / 2 = 1
0
DIP 4 = OFF
8
1 / 2 = 0
1
DIP 5 = ON
16
0 / 2 = 0
0
DIP 6 = OFF
32
0 / 2 = 0
0
DIP 7 = OFF
64
1
6
7
5
4
3
2
8
S2
ON
2
6
x 0 = 0
2
5
x 0 = 0
2
4
x 1 = 16
2
3
x 0 = 0
2
2
x 0 = 0
2
1
x 0 = 0
2
0
x 1 = 1
17
[2]
[1]
NOTES
The PROFIBUS is not interrupted when you remove the EBOX (electronics unit) from
the ABOX (connection unit).