10
Technical Data
General technical data
Operating Instructions – MOVIFIT
®
SC
121
10.2 General technical data
Motor starter
MTS11A015
MTS11A040
Connection voltages
Permitted range
V
Mains
3 x AC 380 V/
AC
400 V
/AC 415 V/AC 460 V/AC 500 V
V
Mains
= AC 380 V
–10% … AC 500 V
+10%
Mains frequency
f
Mains
50 Hz ... 60 Hz ± 10 %
Rated operating current (at 400 V)
I
max
4.0 A
AC
(2 x 2.5 A
AC
)
I
min
0.5 A
(2 x 0.5 A)
I
max
8.7 A
AC
(2 x 4.8 A
AC
)
I
min
0.5 A
(2 x 0.5 A)
Maximum starting frequency
See section "Maximum starting frequency" on page 122
Cycle times
typ. 10 ms
Power connection
Number of motor outputs: 2 (2 x 3 phases), not short-circuit proof
Number of brake outputs: 2, not short-circuit proof
Important: Dangerous contact voltage. The motor and brake outputs
are switched using semiconductors.
Motor startup time
Max. 0.5 s (fast disconnection I > 180% within 1 s)
Soft startup time
0…
0.2
…1 s (free parameter setting)
Reversing time (for single-motor
operation)
0.05...
0.2
...10 s (free parameter setting)
Parameter setting range for motor
current monitoring
0...
150 %
I
Rated
, trigger time 0 < t < 15 s, default value: t = 2 s
Motor current is measured in phase W
Motor protection
Thermistor
Brake control
Integrated brake function (BGE)
Fusing in MOVIFIT
®
16 AT fuses, circuit-breaking capacity: 1.5 kA
Important: When the fuse triggers, for example, on short circuit in the
motor output, you must replace the EBOX. Only SEW-EURODRIVE is
authorized to carry out repairs.
Cable length between MOVIFIT
®
and
motor
Max. 15 m (with SEW hybrid cable, type A)
Hybrid cable shielding
Apply outer shield with EMC cable gland, and apply inner shield with EMC
shield clamp (see section "Installation instructions")
Interference immunity
Meets EN 60947-4-2
Interference emission with
EMC compliant installation
According to class A limit to EN 60947-4-2
Operating mode
DB (EN 600034-1), S3 50%
For max. cycle duration, see section "Maximum starting frequency" on
page 122
Type of cooling (DIN 41751)
Self-cooling
Enclosure
Standard:
IP65 in accordance with EN 60529 (MOVIFIT
®
housing closed and all cable
glands and plug connections sealed)
Hygenic
plus
version:
IP66 in accordance with EN 60529 and IP69K according to DIN 40050-9
(MOVIFIT
®
housing closed and all cable glands sealed according to the
relevant enclosure)
Ambient temperature
–25°C to +40°C (P
Rated
reduction: 3 % I
Rated
per K to max. 60°C)
Climate class
EN 60721-3-3, class 3K3
Storage temperature
–25°C…+85°C (EN 60721-3-3, class 3K3)
Permissible oscillation and impact
load
Meets EN 50178
Overvoltage category
III according to IEC 60664-1 (VDE 0110-1)
Pollution class
2 according to IEC 60664-1 (VDE 0110-1) within the housing
Installation altitude
h
Up to 1,000 m without restrictions
(installation higher than 1000 m: see section "Electrical Installation –
Installation instructions")
Ground (GND)
EBOX "MTS...-....-00" (MOVIFIT
®
-SC): approx. 3.5 kg
ABOX "MTA...-S02.-...-00": approx. 4.5 kg
ABOX "MTA...-S12.-...-00", "MTA...-S22.-...-00": approx. 5.2 kg
ABOX "MTA...-H12.-...-00", "MTA...-H22.-...-00": approx. 6.0 kg
P
i
f
kVA
Hz
n