9
Service
Unit diagnostics
118
Operating Instructions – MOVIFIT
®
SC
UL Protective
functions for
motor 1
84
7
3
Motor 1 switches off when there is an
excess of 600% I
Rated,unit
for more
than 50 ms.
UL Protective
functions for
motor 2
84
8
4
Motor 2 switches off when there is an
excess of 600% I
Rated,unit
for more
than 50 ms.
Motor temper-
ature simula-
tion motor 1
84
9
5
When motor 1 reaches a thermal
utilization of 110%, the unit shuts
down.
•
Reduce the load on the drive
•
Lower ambient temperature
•
Prevent heat build-up
•
Note: You must let the drive cool down
before resetting the fault.
Motor temper-
ature simula-
tion motor 2
84
10
6
When motor 2 reaches a thermal
utilization of 110%, the unit shuts
down.
•
Reduce the load on the drive
•
Lower ambient temperature
•
Prevent heat build-up
•
Note: You must let the drive cool down
before resetting the fault.
Cyclical moni-
toring for
brake release
without drive
enable for
brake 1
89
2
1
Cyclical monitoring has triggered for
brake 1.
Reduce the starting frequency for releasing the
brake without enable.
Cyclical moni-
toring for
release of
brake without
drive enable
for brake 2
89
3
2
Cyclical monitoring has triggered for
brake 2.
Reduce the starting frequency for releasing the
brake without enable.
Fault
Fault
no.
Suberr
or no.
Internal
fault no.
Cause
Troubleshooting