38
Manual – MOVI-PLC® advanced DHE41B/DHF41B/DHR41B Controller
4
Installing the MOVI-PLC® advanced DHR41B controller
Mounting/Installation Instructions
4.5.6
Operating displays of the MOVI-PLC
®
advanced
DHR41B controller in PROFINET mode
There are 4 LEDs (L11, L12, L13, L14) on the DHR41B option card that display the cur-
rent status of the DHR41B option, the PROFINET system and the safety options.
FS LED
LED
L12 (FAILSAFE-STATUS)
indicates the failsafe status on PROFINET.
LED L13
(BUS-FAULT)
The LED
L13 (BUS FAULT)
displays the status of the PROFINET.
NOTE
The LEDs identical with DHE41B (L1 – L10) are described in section "Operating dis-
plays of the MOVI-PLC
®
advanced
DHE41B controller".
Status of
the "FS"
LED
Cause of error
Troubleshooting
Green
•
The safety option is currently perform-
ing a cyclical data exchange with the
F-host (data exchange).
•
Standard operating state.
–
Red
•
Fault status in the safety part.
•
No 24 V_LS supply voltage present.
•
Read diagnostic in F-Host.
•
Eliminate the cause of the fault and
acknowledge in the F-Host.
Off
•
The safety option is currently in the
initialization phase.
•
Check voltage supply.
•
Check configuration of the bus master.
Flashing
red / green
A fault occurred in the safety part; cause
of the fault already remedied acknowl-
edgement required.
Acknowledge fault in the F-Host (reintegra-
tion).
Status of the
LED L13
Cause of error
Troubleshooting
Off
•
PROFINET IO device is currently
exchanging data with the PROFINET
IO controller (Data Exchange).
-
Flashing green
Flashing
green/red
•
The flashing function in the PROFI-
NET IO controller project planning is
activated to visually localize the sta-
tions.
-
Red
•
Connection to the PROFINET IO
controller has failed.
•
PROFINET IO device does not
detect a link
•
Bus interruption
•
PROFINET IO controller is not in
operation
•
Check the PROFINET connection of
the DHR41B option
•
Check the PROFINET IO controller
•
Check the cabling of your PROFINET
network
Yellow
Flashing yellow
•
The STEP 7 hardware configuration
contains a module that is not permit-
ted.
•
Switch the STEP 7 hardware configu-
ration to ONLINE and analyze the sta-
tus of the components of the slots in
the PROFINET IO device.