Manual – MOVI-PLC® advanced DHE41B/DHF41B/DHR41B Controller
53
5
Configuration with the MOVITOOLS® MotionStudio PC software
Project Planning and Startup
Options for engi-
neering access
You have two options to establish engineering access to the MOVI-PLC
®
advanced
DH.41B controller via the Ethernet 2 interface (connector X37):
• For a point-to-point connection, connect the Ethernet 2 interface (X37) of the
MOVI-PLC
®
advanced
DH.41B controller directly to the Ethernet interface of the en-
gineering PC. Use an interface of the engineering PC that is not used for connection
of the PC to the Intranet/Internet. In this way, you avoid reconfiguration of the inter-
face.
• Integrate the MOVI-PLC
®
advanced
DH.41B controller in a network via the Ethernet
2 interface (X37). Edit the configuration file
NetConfig.cfg
in the "System" folder of
the SD memory card to make the necessary address settings. You have the following
options to access the
NetConfig.cfg
configuration file:
– Take the SD memory card out of the MOVI-PLC
®
advanced
DH.41B controller
and insert it into a memory card write/read device.
– First, establish a point-to-point connection to the MOVI-PLC
®
advanced
DH.41B
controller. Then access the
NetConfig.cfg
configuration file via an FTP client.
For older network interfaces, it can be necessary to use a cross cable for the point-
to-point connection.
Address settings
for a point-to-
point connection
• Setting the default IP address:
– De-energize the MOVI-PLC
®
advanced
DH.41B controller.
– Switch the DIP switch to the upper position.
– Re-energize the MOVI-PLC
®
advanced
DH.41B controller. The IP address
192.168.10.4 and the net mask 255.255.255.0 are assigned automatically to the
Ethernet 2 interface of the MOVI-PLC
®
advanced
DH.41B controller.
• Setting other addresses:
By manually editing the section <Ethernet2...> in the
NetConfig.cfg
configuration file
in the "System" folder of the SD memory card, you can set other addresses.
Example:
<!-- Ethernet2 is engineering interface -->
<Ethernet2>
<IPAddress>192.168.10.4</IPAddress>
<Netmask>255.255.255.0>/Netmask>
<Gateway>192.168.10.1</Gateway>
<Nameserver>0.0.0.0</Nameserver>
<Hostname>MOVI-PLC_Eth2>/Hostname>
</Ethernet2>
Switch the DIP switch S1 to the lower position. This ensures that the addresses are
adopted during the next boot process of the MOVI-PLC
®
advanced
DH.1B controller.