Installing the MOVI-PLC® advanced DHE41B controller
Mounting/Installation Instructions
4.3.8
DIP switch S1 default IP address
With the DIP switch S1, you can set a default IP address for the Ethernet 2 connection.
The set IP address is adopted during the next boot process.
4.3.9
SD memory card type OMH41B-T.
The SD memory card is required for operation of the MOVI-PLC
®
advanced
DH.41B
controller. It stores the firmware, the IEC program and user data (e. g. recipes). It is used
in connection with a MOVIAXIS
®
master module for data backup and automatic param-
eterization in case an axis is replaced.
The SD memory card OMH41B-T.. is plugged into the DH.41B option. If delivery also
includes a compact controller, a MOVIAXIS
®
master module or an inverter with installed
DH.41B option, the SD memory card is already installed in the DH.41B option.
The SD memory card is available in 11 different variants (T0 ... T10). The different vari-
ants allow for the execution of different technology functions. The technology level can
be changed by replacing the SD memory card.
Variants
Bootloader
update
When the LEDs L3 and L4 flash orange at a 1 Hz frequency after power-on, a bootloader
update is required. Proceed as follows:
• Do not switch off the power supply during the entire process.
• Press the reset button T1 on the front of the DH.41B option for 3 seconds. When the
bootloader update starts, only LED 4 is flashing.
• The bootloader update has been successful when L4 flashes green.
S1 switch setting
Meaning
Top
Default IP address 192.168.10.4
Bottom
Addresses set in the configuration file (see sec. 4.3.1)
SD memory card OMH41B-T.
Technology
level T0-T10
Part number
Description
T0
1821 204 2
•
Speed control management
•
Positioning, e.g. with the MPLCMotion_MDX library
T1
1821 205 0
Additional technology functions for T0:
•
Electronic cam
•
Electronic gear unit
•
Cam control
T2
1821 206 9
Additional technology functions for T1:
•
Application modules, e.g. Handling, SyncCrane
T3
1821 967 5
Required for path interpolation. Technology level depends on the
required functionality and number of calculated kinematics.
T4
1821 968 3
T5
1821 969 1
T6
1821 970 5
T7
1821 971 3
T8
1821 972 1
T9
1821 974 8
T10
1821 975 6