6
Operation
Error list
Compact Operating Instructions – MOVITRAC
®
LTP-B
45
Code (in-
verter dis-
play)
Code
(MotionStudio
in P0-13)
Error code
status
word
if Bit5 = 1
CANopen
emergency
code
Meaning
Measure
SC-0b5
12
1D
Connection
between inverter
and keypad inter-
rupted.
Check if there is a connection between the inverter and
keypad.
SC-F01
50
0x2B
0x1032
Modbus communi-
cation error
Check the communication settings.
SC-F02
51
0x2F
0x1033
SBus/CANopen
communication
error
Check:
• The communication connection between inverter and
external devices.
• The clearly assigned address per inverter in the net-
work.
SC-F03
52
0x29
0x1034
Fieldbus module
communication
error (fieldbus
side)
Contact SEW‑EURODRIVE Service.
SC-F04
53
0x29
0x1035
Communication
error IO option
card
Contact SEW‑EURODRIVE Service.
SC-F05
54
0x29
0x1036
LTX module com-
munication error
Contact SEW‑EURODRIVE Service.
SC-LoS
The communica-
tion between the
controller and the
power section is
interrupted
Contact SEW‑EURODRIVE Service.
SC-OBS
Communication
failure with other
devices
• A keypad has lost the communication connection to the
inverter.
• The communication connection has been disconnected
in the master-slave network.
• Check the addresses of all inverters in the network.
SF
Switching fre-
quency decreased
The PWM frequency was automatically decreased due to
the heat sink temperature.
SP-Err
31
0x0E
0x101F
Speed error
(
P6-07
)
The difference between the actual speed and setpoint
speed is larger than the percentage value set in
P6-07
.
This error applies only to vector control or control with en-
coder feedback. Set a higher value in
P6-07
.
If you wish to deactivate speed monitoring, set
P6-07
to
100%.
Sto-F
29
0x73
0x101D
STO circuit fault
The safety relay must not transmit test pulses.
Check the voltage source.
STO+ at terminal 12 must be > 18 V.
StoP
The inverter is not
enabled
Activate the enable. Make sure that the enable is
switched on after the STO for the hoist function.
th-Flt
16
0x1F
0x1010
Faulty thermistor
at heat sink.
Contact SEW‑EURODRIVE Service.
type-f
Parameter module
and inverter are
not compatible
The parameter module used is not of type LT BP C.
U-dEF
User settings
loaded.
The parameter set saved in
P6-26
has been restored.
U-torq
25
0x34
0x1019
Minimum torque
limit timeout
(hoist).
The torque threshold has not been exceeded in time.
Increase the time in
P4-16
or the torque limit in
P4-15
.
U-t
09
0x75
0x4209
Undertemperature The ambient temperature is below the specified ambient
temperature range (10.2 Ambient conditions). Provide a
suitable heat source.
U-Volt
07
0xC6
0x3207
DC link under-
voltage
Occurs routinely when switching off the inverter.
Check the line voltage if this occurs while the inverter is
running.
USr-cL
Parameter backup
successfully de-
leted
The parameter set was successfully deleted using
P6-26
.
26879778/EN – 03/2021
Содержание MOVITRAC LTP-B