background image

6

Operation

Error list

Compact Operating Instructions – MOVITRAC

®

 LTP-B

44

Code (in-
verter dis-
play)

Code

(MotionStudio

in P0-13)

Error code

status

word

if Bit5 = 1

CANopen

emergency

code

Meaning

Measure

O-Volt

06

0x07

0x3206

DC link over-
voltage

The error occurs if a high flywheel load or overhauling
load is connected, and the excess regenerative energy is
transferred back to the inverter.
If a fault occurs while stopping or during deceleration, in-
crease the deceleration ramp time 

P1-04

 or connect a

suitable braking resistor to the inverter.
The proportional gain in 

P4-03

 is reduced in vector mode.

In PID control mode, ensure that the ramps are active by
reducing 

P3-11

.

Additionally check if the supply voltage is within the speci-
fied range.
Note: The value of the DC bus voltage can be displayed
in 

P0-20

. A history log is saved in parameter 

P0-36

 in

256 ms intervals prior to a switch off with error.

OI-b

01

0x04

0x2301

Brake channel
overcurrent,
braking resistor
overload

Make sure that the connected braking resistor does not
fall below the minimum value approved for the inverter
(see technical data). Check the braking resistor and the
wiring for possible short-circuits. See also fault reset
delay for O-I and hO-I errors.

OL-br

02

0x04

0x1002

Braking resistor
overload

The software detected an overload at the braking resistor
and switches off to protect the resistor. Make sure that the
braking resistor is operated within the planned parame-
ters before performing any changes to the parameters or
the system. To reduce the load at the resistor, increase
the deceleration time, reduce the loads mass moment of
inertia, or connect additional braking resistors in parallel.
Note the minimum resistor values for the inverter in use.

OF-01

60

0x1C

0x103C

Internal connec-
tion to option
module error.

Check if all optional fieldbus cards correspond to the
same fieldbus type. Contact SEW‑EURODRIVE Service.

OF-02

61

0x1C

0x103D

Option module
fault

Contact SEW‑EURODRIVE Service.

Out-F

26

0x52

0x101A

Inverter output
stage error

• Motor phase failure detection: One or more motor

phases were disconnected at the inverter output.
Check the motor lead.

• Check the EMC-compliant cabling of any external con-

trol cables. Use shielded cables.

• As a test, apply use the internal 24 V supply directly to

the digital inputs, to rule out errors in the signal cable.

• As a test, use the internal 24 V supply directly at the

STO inputs to exclude malfunctions at the STO circuit.

• The safety relay at the STO inputs must not send

pulsed signals.

• Check STO for correct wiring.
• As a test, disconnect the temperature sensor to rule out

errors in the sensor cable.

• As a test, disconnect the motor cable from the inverter

to rule out errors originating in the inverter.

• Contact SEW‑EURODRIVE Service.

P-LOSS

14

0x06

0x310E

Input phase failure An input phase has been separated or interrupted at an

inverter planned for a 3-phase supply.

P-dEF

10

0x09

0x100A

Factory settings
are restored.

Ph-Ib

Unequal voltage
on the input
phases

• Check the device input voltage.
• Check the values in 

P0-22, P0-23, P0-24

.

The values may deviate by a maximum ±10%. Use an in-
put choke if required.

Ph-SEq

45

0x51

Input phases

swapped

The inverter requires the correct input phase sequence
for controlling the fan. Swap any two input phases.

PS-trP

05

0xC8

0x1005

Output stage error
(IGBT self-protec-
tion in case of
overload)

See error 

O-I

.

26879778/EN – 03/2021

Содержание MOVITRAC LTP-B

Страница 1: ...26879778_0321 Drive Technology Drive Automation System Integration Services Compact Operating Instructions MOVITRAC LTP B Edition 03 2021 26879778 EN...

Страница 2: ...SEW EURODRIVE Driving the world...

Страница 3: ...s 7 2 1 Preliminary information 7 2 2 Duties of the user 7 2 3 Target group 7 2 4 Network security and access protection 8 2 5 Designated use 8 2 6 Functional safety technology 9 2 7 Transport 9 2 8 I...

Страница 4: ...he grading and meaning of the signal words for safety notes Signal word Meaning Consequences if disregarded DANGER Imminent hazard Severe or fatal injuries WARNING Possible dangerous situation Severe...

Страница 5: ...alues In this document a period is used to indicate the decimal separator Example 30 5 kg 1 4 Rights to claim under limited warranty Read the information in this documentation This is essential for fa...

Страница 6: ...ing Instructions MOVITRAC LTP B 6 1 8 Copyright notice 2021 SEW EURODRIVE All rights reserved Unauthorized reproduction modifica tion distribution or any other use of the whole or any part of this doc...

Страница 7: ...ons who work on the product pay attention to the following regula tions conditions documentation and information National and regional safety and accident prevention regulations Warning and safety sig...

Страница 8: ...o adapt electronic drive technology components to the particulars of the machinery within wide limits There is a risk that a change of pa rameters that cannot be detected externally may result in unex...

Страница 9: ...an WEEE Directive 2012 19 EU You may use options and accessories from SEW EURODRIVE exclusively in connec tion with products from SEW EURODRIVE 2 6 Functional safety technology The product must not pe...

Страница 10: ...with impermissibly high mechanical vibration and shock loads in excess of the regulations stipulated in EN 61800 5 1 Use at an elevation of more than 3800 m above sea level The product can be used at...

Страница 11: ...ve measure for the product Type of energy transfer Preventive measure Direct power supply Ground connection 2 9 3 Regenerative operation The drive is operated as a generator due to the kinetic energy...

Страница 12: ...product from the voltage supply do not touch any live compo nents or power connections because capacitors might still be charged Observe the following minimum switch off time 10 minutes Observe the c...

Страница 13: ...P B 0015 2B1 4 00 60 Hz Product name MCLTP MOVITRAC LTP B Version B Version status of the device series Recommended motor power 0015 0015 1 5 kW Connection voltage 2 2 200 240 V 5 380 480 V 6 500 600...

Страница 14: ...14 Design 00 00 Standard IP20 housing 10 IP55 NEMA 12K housing 15 IP55 NEMA 12K housing for operation on IT systems 30 IP66 NEMA 4X housing without switch 40 IP66 NEMA 4X housing with switch xH High...

Страница 15: ...urce that is usually limited by fuses or motor protection switches The inverter has the degree of protection IP20 For a higher IP degree of protec tion a suitable enclosure or the IP55 NEMA 12K or the...

Страница 16: ...must be deactivated IP20 devices On sizes 2 and 3 unscrew the EMC screw and the VAR screw on the side of the device 1 2 3034074379 1 EMC screw 2 VAR screw L3 N L2 L L1 Internal EMC Filter Internal Sur...

Страница 17: ...s carry a high DC voltage approx DC 900 V during nominal operation Severe or fatal injuries Before removing the supply cable disconnect the inverter from the power supply and wait at least 10 minutes...

Страница 18: ...tect the braking resistor with a bimetallic relay and set the tripping current IF of the respective braking resistor The flatpack resistors have internal thermal overload protection fuse cannot be re...

Страница 19: ...r or inverter Connection ex ample of the differ ent temperature sensors and their parameterization TF temperature sensor Bimetallic switch TH KTY84 PT1000 24 VIO DI 1 DI 2 DI 3 10 V AI 1 DI 4 0 V AO 1...

Страница 20: ...of the external use of terminals 2 3 and 6 the internally fitted switches and potentiometers can be deacti vated The procedure is described in chapter P0 00 configuration parameters for IP66 NEMA 4X d...

Страница 21: ...0 V 10 0 V PTC th 0 20 mA 4 20 mA 20 4 mA KTY84 PT1000 digital 0 24 V 11 AO 2 DO 2 Analog output 2 10 bit Digital input 2 Analog 0 10 V 10 0 V 0 20 mA 20 0 mA 4 20 mA 20 4 mA Digital 0 24 V max 20 mA...

Страница 22: ...2 NO contact 4 1 6 Communication socket RJ45 NOTICE Voltage at socket not suitable for PCs Damage to PC when connected directly to RJ45 communication socket Use the engineering adapters as described i...

Страница 23: ...ers with degree of protection IP66 NEMA 4X already have openings for supply system motor and control cables 230 V 0 75 5 5 kW 400 V 0 75 11 kW 575 V 0 75 15 kW The following inverters with degree of p...

Страница 24: ...V W M 3 MOVITRAC LT BR 3 1 ND LT 2 F16 K10 5 9007217635508875 1 Line contactor between supply system and inverter 2 Brake 3 Main switch only for device design IP66 NEMA 4X housing with switch MC LTP...

Страница 25: ...17 18 1 3 2 BMK V DC BMV BM V 3 2 3 white red bue red white blue Cut off in the AC circuit Cut off in the DC and AC circuits 18475023883 1 Power supply of the brake rectifier switched simultaneously v...

Страница 26: ...up of the inverter without additional devices Standard keypad MOVITRAC LT 4 5 6 1 2 3 18014401443146379 1 6 digit 7 segment display 4 Navigate button 2 Start button 5 Up button 3 Stop Reset button 6 D...

Страница 27: ...state The parameter edit menu can only be accessed by pressing the Navigate key 4 To switch between the menu for changing parameters and real time display oper ating speed operating current Keep the k...

Страница 28: ...t setting is 50 The setting range can be changed by the user between 5 100 using the F2 function key B As soon as a key on the keypad is pressed the brightness imme diately increases to 100 again Info...

Страница 29: ...l value when changing a pa rameter value Up Down keys The parameter is set to the lowest value When changing P1 01 50 0 is displayed Press the Up Down keys 0 0 is now displayed Changing indi vidual di...

Страница 30: ...ings Firmware update manual and automatic Export inverter parameters to Microsoft Word Monitor the state of the inputs and outputs and the motor Control inverter manual mode Scope Connection to LT She...

Страница 31: ...erating Instructions MOVITRAC LTP B 31 Connection to LT Shell via Bluetooth parameter module MOVITRAC LT L1 L L2 N L3 BR U V W 1 2 3 4 5 6 7 8 9 10 1112 13 14 15 16 17 18 LTP B 1 9007216440559755 1 Pa...

Страница 32: ...are available in MOVITOOLS MotionStudio Monitor upload and download parameters Save parameter settings Monitor the state of inputs outputs and of the motor Connection to MOVITOOLS MotionStudio The co...

Страница 33: ...DHP 11B X31 X32 X33 X30 ON 20 21 7 8 9007216441033995 1 USB A B cable 5 Terminating connector 120 2 USB11A or USM21A 6 Cable splitter 3 RJ10 to RJ10 cable 7 USB A B cable 4 RJ45 cable with open end 8...

Страница 34: ...hanging the control mode in P4 01 when the motor is cold You can also start auto tuning manually via the parameter P4 02 at any time 5 3 Startup for motors WARNING If parameter P4 02 is set to 1 auto...

Страница 35: ...uto Tune 2 34 6 In case of insufficient control performance the control behavior can be optimized via the parameter P7 10 5 3 3 Startup with asynchronous motors or torque motors with VFC torque contro...

Страница 36: ...and deceleration ramps using P1 03 and P1 04 5 Start the automatic motor measurement procedure Auto Tune as described in chapter Auto Tune 2 34 6 Check the magnetizing current P0 14 at half nominal sp...

Страница 37: ...in chapter Auto Tune 2 34 6 Adjust the boost parameters A default setting is P7 14 10 P7 15 10 7 In case of insufficient control performance the control behavior can be optimized via the parameter P7...

Страница 38: ...08 Rated current of the motor P1 09 Rated frequency of the motor P1 10 Rated speed of the motor P1 14 201 Extended parameter menu P4 01 8 BLDC speed control P4 05 Power factor 3 Set the maximum speed...

Страница 39: ...is connected The functions are limited see also chapter 24 V backup mode 6 1 2 Operating state of the inverter The following table shows the messages of the status for an enabled inverter You can tog...

Страница 40: ...L Main Loss Phase failure or supply voltage outside of specification FirE Fire mode Fire mode emergency mode activated The message is displayed al ternately with the current operating state dELAy t De...

Страница 41: ...ults The power rating of the motor corresponds with the power rating of the connected inverter dAtA E 19 0x62 0x1013 Internal memory error DSP Contact SEW EURODRIVE Service dAtA F 17 0x62 0x1011 Inter...

Страница 42: ...or during refer ence travel Check reference cams Check limit switch connection Check reference travel type setting and the parameters required for it Inhibit STO safety circuit open Check to see if th...

Страница 43: ...in P1 11 Set a longer run up time in P1 03 Disconnect the motor from the inverter Enable the in verter again If this fault occurs again check the entire system and completely replace the inverter Faul...

Страница 44: ...ads mass moment of inertia or connect additional braking resistors in parallel Note the minimum resistor values for the inverter in use OF 01 60 0x1C 0x103C Internal connec tion to option module error...

Страница 45: ...sed due to the heat sink temperature SP Err 31 0x0E 0x101F Speed error P6 07 The difference between the actual speed and setpoint speed is larger than the percentage value set in P6 07 This error appl...

Страница 46: ...TRAC LTP B 46 Code in verter dis play Code MotionStudio in P0 13 Error code status word if Bit5 1 CANopen emergency code Meaning Measure USr PS Parameter backup successfully com pleted The parameter s...

Страница 47: ......

Страница 48: ...SEW EURODRIVE Driving the world SEW EURODRIVE GmbH Co KG Ernst Blickle Str 42 76646 BRUCHSAL GERMANY Tel 49 7251 75 0 Fax 49 7251 75 1970 sew sew eurodrive com www sew eurodrive com...

Отзывы: