4.3
Setting the signal mode for FSINA and SOUTA
The signal mode is set with the jumper on jumper strip X2:
●
Inhibit inverter, STR and STL = “0".
●
Disconnect the inverter from the supply.
●
Unscrew and remove terminal strip X1.
●
Use suitable tool, e.g. pointed pliers
or tweezers to change jumpers.
Fig. 8: Jumper strip X2
00404BE N
●
Frequency setpoint input FSINA (X1:2)
Input signal
Jumper
J1
J2
PARA
04 FFSEL
Explanation
0...10 V
(factory setting)
4
factory
setting
–
setpoint potentiometer connection (4.7...10 kW) or
external voltage source 0V = STOP, output
inhibited / 0.1 V = FMIN / 10 V = FMAX
2...10 V
–
external power supply
0...20 mA
4...20 mA
–
“zero live” signal
●
Analog/binary output SOUTA (X1:10)
Input signal
Jumper
J3
J4
PARA
61 SOUT
Explanation
0...10 V
(factory setting)
1
0...10 V
=
0...FMAX
4
Apparent 200 % I
N
= 10 V
5
Active current 200 % I
N
= 10 V
6
Active power 100 % P
D
= 10 V
No function
0
Pulse output, PWM signal
1
Output frequency (0...FMAX) = PWM frequency
(0...100 %)
Pulse output,
binary signal
2
Brake chopper active
3
6 times the output frequency
7
only for interface mode (cannot be activated)
X 2
PE
U
V
W
+Uzk
-Uzk
PTC
*
J1
J2
J3
J4
Jumper
No jumper
Factory setting
4
Commissioning
16
MOVITRAC
®
0500 - Operating Instructions