5.3
Fault information
In the event of a fault the LED H1 will keep flashing (red).
LED H1 (red) flashing
Cause
Remedy / Comments
I
I
once Processor fault
Reset, power down and power up
again
II
II
twice Power down, flashing up to
V
DC link
< 65 V
Automatic reset
Undervoltage, flashing up to
V
mains
< 155 V
Check power supply and power cable
III
III
3 times Trip on overcurrent I > 300% I
N
Check drive
Short circuit
Check motor cable
IIII
IIII
4 times Overvoltage V
DC link
> 408 V
Check supply
Motor regenerating
Check drive, BRC 03 may be
necessary
IIIII
IIIII
5 times Ixt trip motor
Motor overloaded, check drive
(setting parameter 59 ITRIP)
IIIIII
IIIIII
6 times Ixt trip inverter
Inverter overloaded, check drive
IIIIIII
IIIIIII
7 times Motor overtemperature
Motor overloaded, check drive or
check PTC thermistor connection or
jumper X5:-/PTC
IIIIIIII IIIIIIII
8 times Inverter overtemperature
Inverter overloaded, check
installation and ambient conditions
IIIIIIIII IIIIIIIII
9 times EPROM fault
Reset, power down and power up
again
Reset:
To clear a fault message power the unit down and then up again. Wait for minimum 30 seconds
before you power the inverter up again.
Fault memory:
The last four faults are saved and can be read out as display parameters 95 ERR1 in the VAL menu
branch, using the FBG 01 keypad. Details saved are the type of error and the operating time up to
fault occurrence.
If the FBG 01 control unit is plugged in at the time the fault occurs, display parameters VAL 12 F, 13 V,
14 IS, 15 IW and 17 VZK are frozen at the time the fault occurs and can be read out until the unit is
reset.