Manual – Fieldbus Interface INTERBUS UFI11A
51
8
DIP Switches
8
DIP Switches
PD1 – PD5
Binary setting of the process data length
The following example shows how the DIP switch settings are determined for a process
data length of 17. Divide each required process data length by the number two and
make a note of the remainder. The remainder can only be 0 or 1. This corresponds to
the setting of the DIP switches.
PCP 1, 2
You can set the lengths of the PCP channel in words using these two DIP switches. Pos-
sible values are 0, 1, 2 and 4 words.
Process data
length
Please note that INTERBUS does not support all data lengths which can be set. The to-
tal data length of process data and PCP words can be 1 – 10, 12, 14, 16, 24, 26 and 36
words.
If you require a number of words which lies between these settings, the next higher num-
ber must be used. For example, 9PD + 4 words PCP results in 14 words.
AUTO SETUP: See Sec. Quickstart without PC
05376AXX
Fig. 26: DIP switches
Table 1: Example for determining the DIP switch settings for process data width 17
Calculation
Remainder
DIP switch setting
Significance
17
÷
2 = 8
1
X1 = 20 = ON
1
8
÷
2 = 4
0
X2 = 21 = OFF
2
4
÷
2 = 2
0
X3 = 22 = OFF
4
2
÷
2 = 1
0
X4 = 23 = OFF
8
1
÷
2 = 0
1
X5 = 24 = ON
16
PCP 1
PCP 2
OFF
OFF
0
ON
OFF
1
OFF
ON
2
ON
ON
4