![SEW-Eurodrive INTERBUS UFI11A Скачать руководство пользователя страница 29](http://html.mh-extra.com/html/sew-eurodrive/interbus-ufi11a/interbus-ufi11a_manual_1250336029.webp)
Manual – Fieldbus Interface INTERBUS UFI11A
29
5
INTERBUS Interface
The PCP channel can be set to 0, 1, 2, or 4 words. At least one word must be set to
enable parameter data to be exchanged. Higher settings increase the transmission
speed. Fig. 8 shows the possible settings for the PCP channel.
Note that if the total of process data and PCP words exceeds 10 words, you must select
a value equal to or greater than your required data length from the following settings:
0 – 10 words set directly, 12 words, 14 words, 16 words, 24 words and 26 words.
A maximum of 3PDs can be assigned to one station on the SBus.
05378AXX
Fig. 22: Possible settings for PCP words
Содержание INTERBUS UFI11A
Страница 1: ...INTERBUS UFI11A Fieldbus Interface Edition 06 2002 Manual 1052 5114 EN ...
Страница 2: ......
Страница 62: ...13 62 Manual Fieldbus Interface INTERBUS UFI11A Dimensions 13 Dimensions 05114AXX Fig 27 Dimension drawing ...
Страница 65: ......
Страница 66: ......
Страница 67: ......