5
Electrical installation
Connecting the motor via terminal strip
Operating Instructions – EDR..71 – 315, EDRN63 – 315
78
5.15.2
According to wiring diagram C13 with terminal strip /KCC
1. Connect the motor according to the enclosed wiring diagram.
2. Check the maximum cable cross section.
ð
4 mm
2
rigid
ð
4 mm
2
flexible
ð
2.5 mm
2
flexible with conductor end sleeve
3. Check the winding connections in the terminal box and tighten them, if necessary.
4. The stripping length must be 10 – 12 mm.
Arrangement of terminal links with
W
connection
18014399506064139
Arrangement of terminal links with
m
connection
18014399506066059
25896334/EN – 06/2019