3
Motor structure
Nameplate
Operating Instructions – EDR..71 – 315, EDRN63 – 315
24
3.7.2
Additional nameplate for EDR../EDRN.. motors in frequency inverter operation
The following figure shows an example of the additional nameplate for an EDRS motor
in design 2GD for frequency inverter operation (short: additional FI nameplate):
Usys
01.4343157427.0001.14
EDRS71M4/FF/2GD/KCC/TF/AL
400
PTB 11 ATEX 3002/02X
V
VFC
Imax 2.75 A
VFC
Imax 1.57 A
Hz r/min
V
A
Nm
Hz r/min
V
A
Nm
5
90
35
1.40
1.6
5
90
60
0.80
1.6
10
200
54
1.40
1.8
10
200
93
0.80
1.8
25
590
115
1.80
2.5
25
590
200 1.04
2.5
75
2110 346
1.80
2.6
50
1370 400 1.01
2.5
87
2110 400 1.20
1.4
[A]
[B]
[E]
[C]
[D]
[1]
[3]
[4]
[2]
9007212378184715
Line
Information
[1]
System voltage – line voltage of the frequency inverter
[2]
(Voltage Mode Flux Control) Voltage‑controlled control mode of the frequency
inverter and connection type
[3]
EU type examination certificate for frequency inverter operation
[4]
Maximum permitted peak current, e.g. when accelerating with VFC control
mode
[A]
The additional FI nameplate lists the thermal limit characteristic curve of the
motor (item A – E) considering voltage and frequency, see chapter "Limit
characteristic curves of EDR.., EDRN.. motors in inverter opera-
tion" (→
The minimum and maximum frequency can deviate depending on the option.
[B]
[C]
[D]
[E]
25896334/EN – 06/2019