5
Startup
Startup of "standard configuration"
Manual – ECDriveS
®
19
5
Startup
5.1
Startup of "standard configuration"
The prerequisite for starting up ECC-DFC fieldbus controllers in "standard configura-
tion" on the PROFINET IO is that the fieldbus controllers must have already been op-
erated with auto-configuration. This will ensure that the IP address and the PROFINET
device names have been assigned already and are no longer freely configurable.
5.1.1
Mapping the IP address and subnet mask
The network address, the subnet mask, and the PROFINET device name are defined
by auto-configuration. You must configure these parameters accordingly in the higher-
level PROFINET master.
The auto-configuration assigns the node address 192.168.10.20 to the furthest up-
stream ECC-DFC fieldbus controller. Every other fieldbus controller is then assigned a
corresponding node address in ascending order (192.168.10.21, 192.168.10.22).
5.1.2
Mapping the PROFINET device name
The PROFINET device name consists of the following character sequences:
•
"eccdfc"+
•
"plc" or "zpa"+
•
"-"+
•
The value of the third byte in the IP address (192.168.
100
.47)+
•
"-"+
•
The value of the fourth byte in the IP address (192.168.100.
47
)
If the fieldbus controller is put into operation in "reduced ZPA mode", this results in the
following PROFINET device name: eccdfczpa-100-47
25938274/EN – 01/2019