DESCRIPTION

Initialization error

Door blocked error

Anti-crushing in
opening error

Anti-crushing in
closing error

Inversion error

Overcurrent error

Encoder error

NUM.

1

2

3

4

5

6

7

WHAT TO DO

An error occurred during initialisation, in particular, the measured
opening quota is too low. Check the encoder, the connection
between the encoder and mother boards. Make sure the transit
area is free of obstacles. In the event of electronic lock, check
correct operations.
The door cannot open.  Make sure there are no obstacles in the
transit area and that there are no locks (electric or manual) that
block the door.
After three opening and anti-crushing detection attempts.
Make sure there are no obstacles in the transit area.
Make sure that the anti-crushing sensitivity in opening is not too
low. Check the encoder, the connection between the encoder
and mother boards.
After three closing and anti-crushing detection attempts. Make
sure there are no obstacles in the transit area. Make sure that the
anti-crushing sensitivity in opening is not too low. Check the
encoder, the connection between the encoder and mother
boards. 
An inversion error of the movement between the encoder and
motor was detected. Make sure that the motor is  correctly
connected as shown in 

Fig. 30

Motor overload detected. Make sure there are no short circuits
on the motor power cord. Check the motor and replace if
necessary.
Encoder malfunction detected.
Check the encoder, the connection between the encoder and
mother boards.

AV

BL.

BL.

BL.

BL.

BL.

BL.

BL.

OC

OFF

OFF

OFF

OFF

OFF

ON

OFF

LED

L1

OFF

OFF

OFF

ON

ON

ON

ON

L2

OFF

ON

ON

OFF

OFF

ON

ON

L3

ON

OFF

ON

OFF

ON

OFF

ON

Inter lock connection and use

The MILLENNIUM unit is set to work in inter lock mode through
connections to an electronic unit of the same family.
In inter lock mode one door can only open if the other is not mov-
ing, that is, if not in the movement phase.
To inter lock two automatisms proceed as follows 

(Fig. 39)

:

• connect the terminal AUX IN of unit A to the terminal AUX OUT

of unit B

• connect the terminal AUX OUT of unit A to the terminal AUX IN

of unit B

• connect terminal “-“ of the 12Vdc power supply of unit A to the termi-

nal “-“ of the 12Vdc power supply of unit B.

Use  4 x 0.22 shielded wire for connections and do not connect
the shield.

Error Message Table

When open requests come from the both sensors on both doors
an opening priority needs to be set; to do this, set one door as
MASTER and the other as SLAVE.
When simultaneous signals occur, the MASTER door will open.
To select MASTER and SLAVE use the advanced selector.

Fig. 39

UNIT A

UNIT B

22

Installation Instruction

BL. = Blinking

LIGHT MILLENNIUM

Delivery Modality

Close the automatism’s cover following the reverse procedure used to remove it.
Make sure the two fixing screws of the cover are well tightened.
Before to end the automatism’s installation, remember to stick the labels on the sliding wings.
Hand the guarantee and test certificate over filled according to the instructions shown in the certificate.
The certificates must be sent to SESAMO in 8 days from the positive test date. Hand the technical documentations over to
the client.

Содержание LIGHT MILLENIUM

Страница 1: ...Automatisms for sliding doors I N S T A L L A T I O N I N S T R U C T I O N...

Страница 2: ...2...

Страница 3: ...age 15 MILLENNIUM electronic board page 15 Electrical connections page 16 Left Side Electronic Board Connections page 16 Right Side Electronic Board Connections page 17 Led functions page 20 Dip Switc...

Страница 4: ...ble if parts within the automatism are altered or tampered with or if safety devices other than those indicated by the manufacturer are used in the system The automatism installer must provide the aut...

Страница 5: ...on preparation The automatism is prepared to work in different accessory and peripheral configurations Fig 1 shows a com plete installation where the possible automatism box access points for peripher...

Страница 6: ...e centred to the transit area in two wing cross pieces so that the wings meet in the middle of the light space Fig 4 For single wings observe the indications and machine quotas found in Fig 5 Cross pi...

Страница 7: ...and Fig 8 refer to the following table Installation Instruction 7 LIGHT MILLENNIUM HAF Fixed wing height HAS Sliding wing height HCa Automation box height HCo Automation cover height Fig 6 Standard w...

Страница 8: ...omatism components can be moved or removed WARNING Before loosening component lock screws to move components Fig 11 measure the distance of the motor from the head or make marks on the box for correct...

Страница 9: ...e that there is a solid fixture every 600 mm and that the box is fas tened with the slots closest to the two heads WARNING Before completely tightening the screws make sure that the girder is level in...

Страница 10: ...sories Use M8 hexagon head cap screws with flat and notched washers Fig 16 part A Wing assembly Make sure that the anti derailment device is completely low ered by unscrewing the M6 nut Fig 17 C and p...

Страница 11: ...wrench in the wheel eccentric part A Fig 19 loosen the nut using a long handled 24 wrench part B Use the eccentric to move the wing to the required height using the references and on the carriage and...

Страница 12: ...position of the fasteners permits good belt parallelism between the upper and lower branches Verify the correct disposition of the belt fasteners on the carriages in touch with the automatism as indic...

Страница 13: ...djust the limit stops loosen screws as indicated in Fig 22 23 24 part A B then slide the limit to the required posi tion and then tighten the screws If necessary fine adjustments of the wing stop poin...

Страница 14: ...d remove the key the wings are now released To lock the wings again move them to the completely closed position Final operations Before starting the automatism check and perform the following Accurate...

Страница 15: ...ch with minimum con tact opening equal to 3 mm not supplied MILLENNIUM electronic board The meanings of the main electronic board components are listed in Fig 28 Installation Instruction 15 Transforme...

Страница 16: ...irs Left Side Electronic Board Connections Fig 30 summarises terminal connections on the left side of the electronic board 16 Installation Instruction Fig 29 Connectors must be inserted as in Fig 29 L...

Страница 17: ...Selector Jumper between Millenium and external cell amplifier The system has three selectable working models A Millenium amplifier only Jumper close towards INT B External amplifier only Jumper close...

Страница 18: ...connector 12 Vdc 6W max 500mA Real power value may vary from 12 Vdc to about 15 Vdc depending on the resistive load situations connected to these terminals WARNING Do not invert power polarity When th...

Страница 19: ...msec For mode type selection see paragraph JUMPERS Opening signal Wing opening devices can be connected Opening signal Wing opening devices can be connected FUNCTION If the door is closing and the co...

Страница 20: ...g In the event of power failure the equipment continues working powered by the battery Default In the event of power failure the equipment moves the doors to the Stop open position and stays in this c...

Страница 21: ...urn off the equipment and remove the gear motor unscrewing the specific rubber supports Eliminate friction causes and start the equipment again repeating the above described movement Multi logic selec...

Страница 22: ...encoder and mother boards AV BL BL BL BL BL BL BL OC OFF OFF OFF OFF OFF ON OFF LED L1 OFF OFF OFF ON ON ON ON L2 OFF ON ON OFF OFF ON ON L3 ON OFF ON OFF ON OFF ON Inter lock connection and use The M...

Страница 23: ...23...

Страница 24: ...SESAMO srl Str Gabannone 8 10 15030 Terruggia AL Italy Tel 39 0142 403223 Fax 39 0142 403256 www sesamo eu E mail info sesamo eu MAN_LM_EN_4_12_07...

Отзывы: