11(21)
Servodan A/S | Tel +45 7442 4726 | Fax + 45 7442 4035 | [email protected] | www.servodan.com
GB
Technical data
Input:
Power supply ......................... 230 V +10%, 50 Hz
Maximum voltage drop
across dimmer ....................... - 5%
No-load consumption ............ approx. 2.5W
Input impedance:
0-10V and 1-10V ................ 120k
Output:
Minimum load ........................ 100W
Maximum load ....................... 1400VA resistive, inductive and
capacitive
(t<35°C)
Max. output voltage .............. Supply voltage x 0,95 (dissipated
power = max. 1% of the absorbed
power = max. 14W)
Protections: ........................... - electric thermal protection
(105°C) with automatic restart
(Light is reduced to set minimum. It
the temperature does not fall, the
load is switched off).
- single thermal overload protection
(135°C)
Preformance:
Allowed ambient temperature ... see load table
Max. Cover temperature (tc) ... 90°C
Maximum distance to last
push button ........................... 100m.
Wiring of analogue control .... - Control and power circuits of the
dimmer are galvanically isolated.
- The control inputs of the dimmer
comply with the requirements for
safety extra low voltage (SELV). If
the control signals originate from
appliances that also meet the SELV
requirements, no specifi c require
ments in terms of wire diameter
or insulation of the control wires
apply. In that case, the control
wires must be kept away from
230V~ lines (min. 10mm.). In all
other cases the SELV guarantees
do not apply.
Humidity ................................ Designed for use in an environment
with non-condensing atmospheric
humidity (30% - 70%)
Installation ............................. DIN-rail (6 modules)
Weight ................................... approx. 440g
Maximum wire diameter per terminal:
power supply and load ...... 2 x 2,5mm
2
or 1 x 4mm
2
input ................................... 2 x 2,5mm
2
or 1 x 4mm
2
Approval:
According to .......................... EN60669-2-1 and EN55015
Load table
: power in function of the ambient temperature
0
200
400
600
800
1000
1200
1400
1600
(W/VA)
0
25
35
50
60
Temperature (°C)