Installation
AC output cable connection
PE cable should be connected properly and
reliably
Don’t reversely connect PV input cable and
battery input cable to interfaces!
Don’t reversely connect AC Backup load
connector and AC Grid connector.
STEP 1:
Cable OD 16-20mm, pry inner ring out of connector.
STEP 2:
The connector and cable are required to be reliably
connected as shown below.
Order of connection is 1-A
(
Yellow
)
, 2-B
(
Green
)
, 3-
C
(
Red
)
, 4-N
(
Blue
)
,-PE
Cable sectional area 6 mm², stripping length 10
±
0.5mm