2.2. Safety information for the installer
● Installation may only be performed by a qualii ed electrician or
similarly qualii ed person.
●
Work on the sauna control unit may only be performed when the
power has been disconnected.
●
A three-phase shut-off device with a 3 mm contact opening must
be provided during installation. This is provided by the fuse.
●
The sauna control unit must be installed outside the sauna room
at a height of approx. 1.70 m or in accordance with the recom-
mendation issued by the sauna manufacturer. The ambient
temperature must be within a range spanning -10 °C to +40 °C.
●
The heater sensor must be attached in a way that it is not af-
fected by a l ow of air.
●
The heater supply cable must have a minimum cross-section of
2.5 mm
2
and be temperature resistant up to 150 °C.
●
Also comply with the regulations applicable at the installation
location.
●
For your own safety, consult your supplier in the event of prob-
lems that are not explained in sufi cient detail in the installation
instructions.