Programming
19
Doc 01-G0665
Rev A
Programming
01-G0665F11
Figure 16
Switch #1: Operator Programming
POLE #1 – SINGLE/CLOSE BUTTON
ON = Close button only
OFF = Open/Close Button
POLE #2 – RIGHT HAND/LEFT HAND
ON = Left Hand (gate will open to the left)
OFF = Right Hand (gate will open to the right)
(inside of fence looking out)
01-0665F12
Figure 17
POLE #3 – WARNING DEVICE
ON = Warning device will turn on 3 seconds before gate starts to move in either
direction.
OFF = Warning device disabled.
Timer to close is locked out at the factory, to activate the timer to close, move
safety jumper from bottom two pins (show illustration) to top two pins. Then set
time per the chart below. During normal operation, if the operator stops on a limit,
or mid travel, the operator will time out per the chart on page 20 (Table 8) and
automatically close. To lock the timer to close program and disable, simply return
the jumper to the bottom two pins, or turn on all pins of SW#2.
IMPORTANT NOTE:
When using master/slave, only set the time for the master
operator. The slave operator must be set to disable position (all poles on).
POLE #4 – MASTER/SLAVE – SINGLE UNIT
ON = Master or single Unit
OFF = Slave unit
RED LED INFORMATION
Continuous ON = Unit is on a limit
Blinking 1 flash per second = Normal operation (gate travel or mid-stop)
Blinking 2 flashes per second = Entrapment level 1 (operator reverse to limit)